Pepperl+Fuchs 106262

CJ4-12GK-N

Capacitive sensor

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Series: Cylindrical type, Housing material: PBT, Output type: 2-wire, Installation: non-flush, Type of voltage: DC, Connection type: cable PVC , 2 m, Degree of protection: IP68fa

Technical parameters

Switching function: Normally open (NO)
Output type: NAMUR
Rated operating distance: 4 mm
Installation: non-flush
Assured operating distance: 0 ... 2.88 mm
Output type: 2-wire
Installation conditions: A: 20 mm
Installation conditions: B: 80 mm
Installation conditions: C: 12 mm
Installation conditions: F: 70 mm
Nominal voltage: 8.2 V (Ri approx. 1 kΩ)
Operating voltage: 7 ... 12 V
Switching frequency: 0 ... 1 Hz
Current consumption: Measuring plate not detected: ≤ 1 mA
Current consumption: Measuring plate detected: ≥ 2.4 mA
MTTFd: 3299 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
Standard conformity: NAMUR: EN 60947-5-6:2000 IEC 60947-5-6:1999
Standard conformity: Standards: EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
ATEX approval: Equipment protection level Ga: TÜV 03 ATEX 2003 X
ATEX approval: Equipment protection level Gb: TÜV 03 ATEX 2003 X
ATEX approval: Equipment protection level Da: TÜV 03 ATEX 2003 X
FM approval: Control drawing: 116-0165
UL approval: cULus Listed, General Purpose
CSA approval: cCSAus Listed, General Purpose
CCC approval: CCC approval / marking not required for products rated ≤36 V
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Connection type: cable PVC , 2 m
Core cross-section: 0.34 mm2
Housing material: PBT
Sensing face: PBT
Degree of protection: IP68
Cable: Cable diameter: 4.8 mm ± 0.2 mm
Cable: Bending radius: > 10 x cable diameter
Use in the hazardous area: see instruction manuals

Logistic parameters

ECCN:
Country of Origin: ID
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m