Article image KL6811

Beckhoff KL6811

KL6811 | DALI/DSI master and power supply terminal

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The KL6811 enables the connection of up to 64 DALI slaves. The KS2000 software enables simple configuration via a PC that is directly coupled with the Bus Coupler via an RS232 interface or via the fieldbus. The integrated power supply unit generates an electrically isolated 24 V DC output voltage. No further components are required for the operation of the DALI slaves. The KL6811 operates fieldbus-independent.

Technical parameters

Technology: DALI/DSI
Number of channels: 1
Slaves/groups: max. 64/max. 16
Data transfer channels: 1
Data transfer standard: DALI
Data transfer rates: 1200 baud
Current consumption K-bus: typ. 55 mA
Current consumption power contacts: typ. 30 mA + load
Short-circuit proof: yes, automatic restart
Electrical isolation: 500 V (K-bus/DALI-bus)
Bit width in the process image: input/output: 4 x 8 bit user data, 1 x 8 bit control/status (up to 5 x 8 bit user data are possible)
Configuration: via the Bus Coupler or the controller
Nominal voltage: 24 V DC (-15 %/+20 %)
Input voltage: 24 V DC (-15 %/+20 %)
Insulation voltage: DALI-bus/K-bus: 1,500 V DC, DALI-bus/power contacts: 1,500 V DC
DALI/DSI: standards-compliant, open circuit voltage 11.5…15 V DC
DALI power supply: max. 130 mA
Surge voltage resistance: constant load 275 V ACrms
Special features: connection of up to 64 DALI slaves; TwinCAT library: TwinCAT PLC DALI
Weight: approx. 80 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals
Approvals: CE, UL, Ex

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m