KL4021
KL4021 | 1-channel analog output terminal 4…20 mA
The KL4021 analog output terminal generates analog output signals in the range from 4 to 20 mA. The power is supplied to the process level with a resolution of 12 bits and is electrically isolated. Ground potential for the output channels of a Bus Terminal is common with the 24 V DC supply. The output stages are powered by the 24 V supply. The run LEDs give an indication of the data exchange with the Bus Coupler.
| Technology: | single-ended | 
| Number of outputs: | 1 | 
| Power supply: | 24 V DC via power contacts (alternative 15 V DC with power supply terminal KL9515) | 
| Signal current: | 4…20 mA | 
| Load: | < 500 Ω | 
| Output error: | < ±0.1 % (relative to end value) | 
| Resolution: | 12 bit | 
| Conversion time: | ~ 1.5 ms | 
| Electrical isolation: | 500 V (K-bus/signal voltage) | 
| Current consumption power contacts: | typ. 30 mA + load | 
| Current consumption K-bus: | typ. 60 mA | 
| Bit width in the process image: | output: 1 x 16 bit data (1 x 8 bit control/status optional) | 
| Configuration: | no address or configuration setting | 
| Weight: | approx. 80 g | 
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C | 
| Relative humidity: | 95 %, no condensation | 
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. class/installation pos.: | IP 20/variable | 
| Pluggable wiring: | for all KSxxxx Bus Terminals | 
| Approvals: | CE, UL, Ex, GL | 
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg | 
| Length: | 0.00 m | 
| Width: | 0.00 m | 
| Height: | 0.00 m |