Article image KL3454

Beckhoff KL3454

KL3454 | 4-channel analog input terminal 4…20 mA

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The KL3454 analog input terminal processes signals in the range between 4 and 20 mA. The current is digitised to a resolution of 12 bits and is transmitted, in an electrically isolated form, to the higher-level automation device. In the KL3454, the four inputs are 2-wire versions and have a common ground potential. The 24 V power contact is connected to the terminal, in order to enable the connection of 2-wire sensors without external supply. The power contacts are connected through. The reference ground for all inputs is the 0 V power contact. Overload is detected. The terminal status is relayed to the controller via the K-bus. The run LEDs indicate the data exchange with the Bus Coupler, the error LEDs overload or wire breakage.

Technical parameters

Number of inputs: 4
Power supply: via the K-bus
Signal current: 4…20 mA
Technology: single-ended
Internal resistance: < 85 Ω
Common-mode voltage UCM:
Resolution: 12 bit
Conversion time: ~ 2 ms
Measuring error: < ±0.3 % (relative to full scale value)
Surge voltage resistance: 30 V DC
Electrical isolation: 500 V (K-bus/signal voltage)
Current consumption power contacts: only load
Current consumption K-bus: typ. 85 mA
Bit width in the process image: input: 4 x 16 bit data (4 x 8 bit control/status optional)
Configuration: no address or configuration setting
Special features:
Weight: approx. 55 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals
Approvals: CE, UL, Ex, GL

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m