Article image KL3312

Beckhoff KL3312

KL3312 | 2-channel thermocouple input terminal with open-circuit recognition

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The KL3312 analog input terminal allows thermocouples to be connected directly. The Bus Terminal’s circuitry can operate thermocouple sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminals. The KL3312 can also be used for mV measurement.

Technical parameters

Number of inputs: 2
Power supply: via the K-bus
Technology: 2-wire
Thermocouple sensor types: types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Connection method: 2-wire
Measuring range: in the range defined in each case for the sensor (default setting: type K; -100…+1370 °C); mV measurement: ±30 mV…±120 mV
Resolution: 0.1 °C per digit
Conversion time: ~ 250 ms
Wiring fail indication: yes
Measuring error: < ±0.5 % (relative to full scale value)
Electrical isolation: 500 V (K-bus/signal voltage)
Current consumption power contacts: – (no power contacts)
Current consumption K-bus: typ. 65 mA
Bit width in the process image: input: 2 x 16 bit data (2 x 8 bit control/status optional)
Configuration: no address setting, configuration via Bus Coupler or controller
Weight: approx. 70 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Approvals: CE, UL, Ex

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m