Description

The KL3311 analog input terminal allows thermocouples to be connected directly. The Bus Terminal’s circuitry can operate thermocouple sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminals. The KL3311 can also be used for mV measurement.

Technical parameters

Number of inputs: 1
Power supply: via the K-bus
Technology: 2-wire
Thermocouple sensor types: types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Connection method: 2-wire
Measuring range: in the range defined in each case for the sensor (default setting: type K; -100…+1370 °C); mV measurement: ±30 mV…±120 mV
Conversion time: ~ 200 ms
Wiring fail indication: yes
Resolution: 0.1 °C per digit
Measuring error: < ±0.5 % (relative to full scale value)
Electrical isolation: 500 V (K-bus/signal voltage)
Current consumption power contacts: – (no power contacts)
Current consumption K-bus: typ. 65 mA
Bit width in the process image: input: 1 x 16 bit data (1 x 8 bit control/status optional)
Configuration: no address setting, configuration via Bus Coupler or controller
Special features: electrically isolated
Weight: approx. 70 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Approvals: CE, UL, Ex

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m