Article image KL3208-0010

Beckhoff KL3208-0010

KL3208-0010 | HD Bus Terminal, 8-channel input terminal PT1000, Ni1000 (RTD); NTC sensors, potentiometers

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The KL3208-0010 analog input terminal enables connection of eight resistance sensors. The Bus Terminal’s circuitry can handle sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The Bus Terminal’s standard settings are: resolution 0.01 °C within the temperature range of PT/Ni1000 sensors. The error LEDs indicate sensor faults (e.g. a broken wire).

Technical parameters

Number of inputs: 8
Power supply: via the K-bus
Technology: 2-wire
Sensor types: PT1000 (default), Ni1000, potentiometer 1/5/10 kΩ, NTC 1.8 k/2.2 k/3 k/5 k/10 k/20 k/100 k
Connection method: 2-wire
Measuring range: -50…+150 °C (depending on sensor type)
Conversion time: ~ 1 s
Measuring current: typ. < 0.5 mA
Resolution: 0.01 °C per digit
Measuring error: -20…+60 °C: ±0.25 °C at 25 °C ambient temperature; -50…+150 °C: ±1.5 °C (for PT/Ni sensors)
Electrical isolation: 500 V (K-bus/signal voltage)
Current consumption power contacts:
Current consumption K-bus: typ. 85 mA
Bit width in the process image: input: 8 x 16 bit data (8 x 8 bit control/status optional)
Configuration: no address setting, configuration via Bus Coupler or controller
Conductor types: solid wire, stranded wire and ferrule
Conductor connection: solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver
Rated cross-section: solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm²
Special features: open-circuit recognition, cable resistance calibration, particularly suitable for building automation
Weight: approx. 75 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Approvals/markings: CE, UL, ATEX
Ex-Marking: II 3 G Ex nA IIC T4 Gc

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m