KL3204-0030
KL3204-0030 | 4-channel input terminal NTC (10 kΩ)
The KL3204-0030 analog input terminal enables four NTC resistance sensors to be connected directly. The Bus Terminal's circuitry can handle sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The standard setting of the Bus Terminal is a resolution of 0.1 °C in the temperature range of the NTC 10 kΩ sensors. The error LEDs indicate sensor faults (e.g. a broken wire). The KL3204 combines four channels in a single housing.
Number of inputs: | 4 |
Power supply: | via the K-bus |
Technology: | 2-wire |
Sensor types: | NTC10k (carel characteristic curve, 0 °C: 27280 Ω) |
Connection method: | 2-wire |
Resolution: | 0.1 °C per digit |
Conversion time: | ~ 250 ms |
Measuring current: | typ. < 0.5 mA |
Measuring error: | < ±1 °C |
Electrical isolation: | 500 V (K-bus/signal voltage) |
Current consumption power contacts: | – (no power contacts) |
Current consumption K-bus: | typ. 60 mA |
Bit width in the process image: | input: 4 x 16 bit data (4 x 8 bit control/status optional) |
Configuration: | no address setting, configuration via Bus Coupler or controller |
Special features: | open-circuit recognition |
Weight: | approx. 70 g |
Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Approvals/markings: | CE, UL |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |