Article image KL3204

Beckhoff KL3204

KL3204 | 4-channel input terminal PT100 (RTD)

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The KL3204 analog input terminal allows resistance sensors to be connected directly. The Bus Terminal’s circuitry can operate the sensors using 2-wire connection techniques. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The Bus Terminals standard settings are: resolution 0.1 °C in the temperature range of PT100 sensors. The error LEDs indicate sensor faults (e.g. a broken wire). The KL3204 version combines four channels in one housing.

Technical parameters

Number of inputs: 4
Power supply: via the K-bus
Technology: 2-wire
Sensor types: PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (e.g. potentiometer, 10 Ω…1.2/5 kΩ)
Connection method: 2-wire
Measuring range: -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors)
Resolution: 0.1 °C per digit
Conversion time: ~ 250 ms
Measuring current: typ. 0.5 mA
Measuring error: < ±1 °C
Electrical isolation: 500 V (K-bus/signal voltage)
Current consumption power contacts: – (no power contacts)
Current consumpt. K-bus: typ. 60 mA
Bit width in the process image: input: 4 x 16 bit data (4 x 8 bit control/status optional)
Configuration: no address setting, configuration via Bus Coupler or controller
Special features: open-circuit recognition
Weight: approx. 70 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals
Approvals: CE, UL, Ex, GL

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m