KL3064
KL3064 | 4-channel analog input terminal 0…10 V
The KL3064 analog input terminal handles signals in the range from 0 to 10 V. The voltage is digitised to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of a Bus Terminal have a common ground potential. The KL3064 combines four channels in one housing. The run LEDs give an indication of the data exchange with the Bus Coupler.
Number of inputs: | 4 |
Power supply: | via the K-bus |
Signal voltage: | 0…10 V |
Technology: | single-ended |
Internal resistance: | > 200 kΩ typ. |
Common-mode voltage UCM: | – |
Resolution: | 12 bit |
Conversion time: | ~ 4 ms |
Measuring error: | < ±0.3 % (relative to full scale value) |
Electrical isolation: | 500 V (K-bus/signal voltage) |
Current consumption power contacts: | – (no power contacts) |
Current consumption K-bus: | typ. 85 mA |
Bit width in the process image: | input: 4 x 16 bit data (4 x 8 bit control/status optional) |
Configuration: | no address or configuration setting |
Weight: | approx. 80 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all KSxxxx Bus Terminals |
Approvals: | CE, UL, Ex, GL |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |