KL3044
KL3044 | 4-channel analog input terminal 0…20 mA
The job of the KL3044 analog input terminal is to transmit analog measurement signals with electrical isolation to the automation device. The input electronics is independent of the supply voltage of the power contacts. The ground connection is the reference potential for the inputs. The error LEDs indicate an overload condition. The KL3044 combines four channels in one housing.
Number of inputs: | 4 |
Signal current: | 0…20 mA |
Technology: | single-ended |
Internal resistance: | 80 Ω + 0.7 V |
Common-mode voltage UCM: | – |
Resolution: | 12 bit |
Conversion time: | ~ 4 ms |
Measuring error: | < ±0.3 % (relative to full scale value) |
Surge voltage resistance: | 35 V max. |
Electrical isolation: | 500 V (K-bus/signal voltage) |
Current consumption power contacts: | – (no power contacts) |
Current consumption K-bus: | typ. 65 mA |
Bit width in the process image: | input: 4 x 16 bit data (4 x 8 bit control/status optional) |
Configuration: | no address or configuration setting |
Weight: | approx. 70 g |
Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all KSxxxx Bus Terminals |
Approvals: | CE, UL, Ex, GL |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |