KL3002
KL3002 | 2-channel analog input terminal -10…+10 V
The KL3002 analog input terminal handles signals in the range from -10 to +10 V. The voltage is digitised to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the Bus Terminal have differential inputs and possess a common, internal ground potential. The light emitting diodes give an indication of the data exchange with the Bus Coupler.
Number of inputs: | 2 |
Power supply: | via the K-bus |
Signal voltage: | -10…+10 V |
Technology: | differential input |
Internal resistance: | > 200 kΩ |
Common-mode voltage UCM: | 35 V max. |
Resolution: | 12 bit (for 0…10 V range: resolution 11 bit) |
Conversion time: | ~ 2 ms |
Measuring error: | < ±0.3 % (relative to full scale value) |
Electrical isolation: | 500 V (K-bus/signal voltage) |
Current consumption power contacts: | – (no power contacts) |
Current consumption K-bus: | typ. 65 mA |
Bit width in the process image: | input: 2 x 16 bit data (2 x 8 bit control/status optional) |
Configuration: | no address or configuration setting |
Weight: | approx. 70 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all KSxxxx Bus Terminals |
Approvals: | CE, UL, Ex |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |