KL2732
KL2732 | 2-channel triac output terminal 12…230 V AC
The KL2732 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac. As a semiconductor switch, it is not subject to wear. The KL2732 has two mutually locked outputs and operates with two potential-free switches. The terminal is most suitable for reverse motors.
| Connection technology: | 2-wire |
| Number of outputs: | 2 x make contacts (without power contacts) |
| Rated load voltage: | 12…230 V AC |
| Load type: | ohmic, inductive |
| Max. output current: | 1 A (leakage current: typ. 0.8 mA, max. 1.5 mA) per channel |
| Frequency range: | 47…63 Hz |
| Surge voltage protection: | > 275 V AC |
| Peak current: | 40 A (16 ms), 3 A (30 s) |
| Switch-off time: | T/2 |
| Residual voltage: | max. 1.5 V |
| Electrical isolation: | 500 V (K-bus/field voltage), 3750 V AC (1 min.) |
| Leakage current (OFF state): | typ. 0.8 mA, max. 1.5 mA |
| Current consumption power contacts: | – (no power contacts) |
| Current consumption K-bus: | typ. 10 mA |
| Bit width in the process image: | 2 outputs |
| Configuration: | no address or configuration setting |
| Special features: | reverse motors (blinds) |
| Weight: | approx. 55 g |
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Pluggable wiring: | for all KSxxxx Bus Terminals |
| Approvals/markings: | CE, GL |
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |