Article image KL2732

Beckhoff KL2732

KL2732 | 2-channel triac output terminal 12…230 V AC

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The KL2732 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac. As a semiconductor switch, it is not subject to wear. The KL2732 has two mutually locked outputs and operates with two potential-free switches. The terminal is most suitable for reverse motors.

Parametry techniczne

Connection technology: 2-wire
Number of outputs: 2 x make contacts (without power contacts)
Rated load voltage: 12…230 V AC
Load type: ohmic, inductive
Max. output current: 1 A (leakage current: typ. 0.8 mA, max. 1.5 mA) per channel
Frequency range: 47…63 Hz
Surge voltage protection: > 275 V AC
Peak current: 40 A (16 ms), 3 A (30 s)
Switch-off time: T/2
Residual voltage: max. 1.5 V
Electrical isolation: 500 V (K-bus/field voltage), 3750 V AC (1 min.)
Leakage current (OFF state): typ. 0.8 mA, max. 1.5 mA
Current consumption power contacts: – (no power contacts)
Current consumption K-bus: typ. 10 mA
Bit width in the process image: 2 outputs
Configuration: no address or configuration setting
Special features: reverse motors (blinds)
Weight: approx. 55 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals
Approvals/markings: CE, GL

Parametry logistyczne

ECCN:
Kraj pochodzenia:
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m