Article image KL2692

Beckhoff KL2692

KL2692 | Cycle monitoring terminal (watchdog)

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The KL2692 Bus Terminal monitors a bit that is toggled by the controller during each cycle. If the toggle signal fails, the controller switches off two potential-free relay circuits in order to prevent damage to the machine. Failure of the toggle signal may be caused by the PLC cycle stopping, by a fault in the bus cable or connector, or by a fault in a bus device. The cycle monitoring time can be parameterised. The Bus Terminal has an enable input that enables the relay to be switched on if a correct toggle signal is detected.

Technical parameters

Connection technology: 2-wire
Number of outputs: 2 potential-free relay outputs (normally-open contacts)
Number of inputs: 2 digital 24 V inputs
Rated load voltage: 30 V DC
Max. output current: 3 A per channel
Ohmic switching current: 5 A AC/DC per channel
Inductive switching current: 2 A AC/DC per channel
Minimum permitted load: 10 mA at 5 V DC
Electrical isolation: 500 V (K-bus/field potential)
Current consumption power contacts:
Current consumption K-bus: typ. 165 mA
Bit width in the process image: 2 x 8 bit data, 1 x 8 bit control/data
Operating cycles mech. (min.): 2 x 107
Operating cycles electr. (min.): 1 x 105 (5 A/30 V DC)
Configuration: via the Bus Coupler or the controller
Weight: approx. 60 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals
Approvals: CE, UL

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m