The KL2184 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation. The KL2184 version has four 0 V (ground) switching outputs and generates load currents with outputs that are resistant to overload and short-circuit. The Bus Terminal contains four channels that indicate their signal state by means of light emitting diodes.

Technical parameters

Connection technology: 2-/3-wire
Number of outputs: 4
Rated load voltage: 24 V DC (-15 %/+20 %)
Load type: ohmic, inductive, lamp load
Max. output current: 0.5 A (short-circuit-proof) per channel
Short circuit current: < 7 A
Breaking energy: < 100 mJ/channel
Reverse voltage protection: yes
Electrical isolation: 500 V (K-bus/field potential)
Current consumption power contacts: typ. 30 mA + load
Current consumpt. K-bus: typ. 9 mA
Bit width in the process image: 4 outputs
Configuration: no address or configuration setting
Weight: approx. 70 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all KSxxxx Bus Terminals