IE3312
IE3312 | 4-channel analog input thermocouple
The IE3312 analog input module permits four thermocouples to be directly connected. The module’s circuit can operate thermocouple sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through a temperature measurement in the connecting plugs. This means that standard extension leads can be connected. The IE3312 can also be used for mV measurement.
Number of inputs: | 4 |
Connection method: | screw type M12, 2-wire connection for thermocouple |
Sensor types: | types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement |
Measuring range: | depending on sensor type; preset value is type K, -100…+1370 °C |
Resolution: | 0.1 °C per digit |
Measuring error: | < ±0.5 % (relative to full scale value) |
Conversion time: | approx. 250 ms (configurable up to 70 ms) |
Nominal voltage: | 24 V DC (-15 %/+20 %) |
Input filter: | 5 variations, configurable |
Current consumption from US (without sensor current): | 40 mA |
Power supply connection: | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Bit width in the process image: | input: 4 x 16 bit data (4 x 8 bit control/status optional) |
Electrical isolation: | channels/control voltage: 500 V, between the channels: no, control voltage/fieldbus: yes, via IP-Link |
Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals: | CE, UL |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |