Article image IE3312

Beckhoff IE3312

IE3312 | 4-channel analog input thermocouple

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The IE3312 analog input module permits four thermocouples to be directly connected. The module’s circuit can operate thermocouple sensors using the 2-wire technique. Linearisation over the full temperature range is realised with the aid of a microprocessor. The temperature range can be selected freely. The error LEDs indicate a broken wire. Compensation for the cold junction is made through a temperature measurement in the connecting plugs. This means that standard extension leads can be connected. The IE3312 can also be used for mV measurement.

Technical parameters

Number of inputs: 4
Connection method: screw type M12, 2-wire connection for thermocouple
Sensor types: types J, K, L, B, E, N, R, S, T, U (default setting type K), mV measurement
Measuring range: depending on sensor type; preset value is type K, -100…+1370 °C
Resolution: 0.1 °C per digit
Measuring error: < ±0.5 % (relative to full scale value)
Conversion time: approx. 250 ms (configurable up to 70 ms)
Nominal voltage: 24 V DC (-15 %/+20 %)
Input filter: 5 variations, configurable
Current consumption from US (without sensor current): 40 mA
Power supply connection: feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin
Bit width in the process image: input: 4 x 16 bit data (4 x 8 bit control/status optional)
Electrical isolation: channels/control voltage: 500 V, between the channels: no, control voltage/fieldbus: yes, via IP-Link
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 65/66/67 (conforms to EN 60529)/variable
Approvals: CE, UL

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m