IE2808 | 16-channel digital output 24 V DC, I. MAX. 0.5 A (∑ 4 A)
The IE2808 digital output module connects the binary control signals from the automation unit on to the actuators at the process level. The sixteen outputs handle load currents of up to 0.5 A each, although the total current is limited to 4 A. This makes these modules particularly suitable for applications in which not all of the outputs are active at the same time, or in which not all of the actuators draw 0.5 A current. An output short-circuit is recognised and passed on to the controller. The signal state is indicated in groups by means of light emitting diodes. The signal connection is realised by the 25-pin D-sub socket. All outputs are short-circuit-proof, protected against inverse connection and can be diagnosed.
Number of outputs: | 16 |
Output connections: | D-sub socket, 25-pin |
Load type: | ohmic, inductive, lamp load |
Nominal output voltage: | 24 V DC (-15 %/+20 %) |
Max. output current: | 0.5 A per channel, individually short-circuit-proof, total current max. 4 A |
Short circuit current: | max. 1.5 A |
Auxiliary power current: | typ. 30 mA |
Current consumption from US (without sensor current): | 25 mA |
Power supply connection: | feed: 1 x M8 male socket, 4-pin; downstream connection: 1 x M8 female socket, 4-pin |
Error handling: | fault acknowledgement by master required |
Bit width in the process image: | 16 outputs, 16 inputs (diagnostics) optional: control/status |
Electrical isolation: | channels/control voltage: no, between the channels: no, control voltage/fieldbus: yes, via IP-Link |
Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals: | CE, UL |
ECCN: | |
Country of Origin: | |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |