Article image EPP6001-0002

Beckhoff EPP6001-0002

EPP6001-0002 | 1-channel serial interface, RS232, RS422/RS485

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EPP6001-0002 serial interface module allows the connection of devices with an RS232 or RS422/RS485 interface. The module transmits the data in a fully transparent manner to the higher-level automation device. The active serial communication channel functions independently of the higher-level bus system in full duplex mode at up to 115,200 baud, while a 864 byte receive buffer and a 128 byte send buffer are available. The 1-channel version has an increased end device power supply of up to 1 A, the connector assignment depends on the selected interface. The two integrated digital inputs/outputs allow the connection of additional sensors/actuators in order, for example, to trigger the reading process of the barcode reader or, depending on the result, to initiate an action. In conjunction with the TwinCAT Virtual Serial COM Driver the EPP6001-0002 can be used as a normal Windows COM interface.

Technical parameters

Data transfer channels: 1
Data transfer rates: 300…115,200 baud; 9600 baud (8 bit, no parity, 1 stop bit) is preset
Number of digital inputs/outputs: 2, 24 V DC, 10 µs/0.5 A
Connection method: M12, screw type
Nominal voltage: 24 V DC (-15 %/+20 %)
Bus interface: 2 x M8 socket, shielded, screw type, EtherCAT-P-coded
Distributed clocks:
Bit distortion: < 3 %
Cable length: RS232: max. 15 m; RS422/RS485: approx. 1000 m
Data buffer: 864 bytes receive buffer, 128 bytes transmit buffer
Sensor supply: +5 V DC, 1 A
Current consumption from US: typ. 100 mA
Power supply connection: not necessary
Bit width in the process image: 22 x 8 bit input, 22 x 8 bit output, 16 bit control, 16 bit status
Electrical isolation: 500 V
Special features: easy integration of serial end devices
Weight: approx. 165 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 65/66/67 (conforms to EN 60529)/variable
Approvals/markings: CE, UL

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m