Article image ELX4181

Beckhoff ELX4181

ELX4181 | 1-channel analog output terminal 0/4…20 mA, single-ended, HART, 16 bit, Ex i

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The ELX4181 analog output terminal is used for the direct control of intrinsically safe field devices located in hazardous areas classified Zone 0/20 or 1/21. It can optionally function as a 0…20 mA or 4…20 mA interface and enables communication with the help of the HART protocol (Highway Adressable Remote Transducer). The HART protocol enables two-way communication through digital data transfer via the analog interface. The TwinCAT FDT container enables the integration of field device DTMs into TwinCAT Engineering, so that the device configuration and diagnostic functions are available directly within the development environment. The ELX4181 is supplied via the power contacts of the ELX9560 power feed terminal. Error LEDs signal overload and wire breakage, and additional LEDs provide information about the state of the HART communication and indicate any communication errors.

Technical parameters

Technology: intrinsically safe actuators with HART support (version 7)
Signal current: 0/4…20 mA
Number of outputs: 1 (single-ended)
Connection method: 2-wire
Load: < 500 Ω
Resolution: 16 bit (incl. sign)
Conversion time: typ. 1 ms
Supply voltage electronics: 24 V DC (via power contacts), ELX9560 power supply
Current consumption power contacts: typ. 10 mA + load
Current consumption E-bus: typ. 95 mA
Distributed clocks: yes
Special features: parameterisable watchdog, activatable user calibration
Weight: approx. 60 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/see documentation
Approvals/markings: CE, UL, ATEX, IECEx, cFMus
Ex-Marking: ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I cFMus: AIS Class I, II, III, Division 1, Groups A thru G Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx nA [ia Ga] IIC T4 Gc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC T4

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m