Article image ELX1054

Beckhoff ELX1054

ELX1054 | 4-channel digital input terminal NAMUR, Ex i

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The ELX1054 digital input terminal acquires signals from NAMUR field devices according to EN 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way, a wire breakage or short-circuit can be detected in addition to the switching state. The LEDs indicate signal or any error states, channel by channel.

Technical parameters

Technology: DC switching amplifier
Specification: IEC 60947-5-6
Number of inputs: 4
Connection method: 2-wire
Open circuit voltage: typ. 8.2 V DC
“0” signal current: ≤ 1.2 mA
“1” signal current: ≥ 2.1 mA
Switching hysteresis: 200 µA
Short-circuit current: typ. 7 mA
Fault detection: I ≤ 200 µA (cable break), I ≥ 6.3 mA (short circuit)
Max. switching frequency: typ. 5 kHz (duty factor 50 %)
Supply voltage electronics: 24 V DC (via power contacts), ELX9560 power supply
Current consumption power contacts: typ. 15 mA + load
Current consumption E-bus: typ. 70 mA
Weight: approx. 55 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/see documentation
Approvals/markings: CE, UL, ATEX, IECEx, cFMus
Ex-Marking: ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I cFMus: AIS Class I, II, III, Division 1, Groups A thru G Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx nA [ia Ga] IIC T4 Gc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC T4

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m