Description

The Interbus slave terminal facilitates data exchange between EtherCAT and Interbus. For both bus systems the terminal “mirrors” up to 32 word input and 32 word output to the respective other system. The outputs are written to the inputs of the other bus with minimum delay. The terminal can use the Interbus protocol up to a baud rate of 2 Mbits. Due to the connection via EtherCAT, no PCI slots are required in the PC.

Technical parameters

Technology: Interbus slave terminal
Fieldbus: Interbus, max. 400 m between 2 stations at 500 kbit/s
Number of fieldbus channels: 1
Data transfer rates: 500 kbits, 2 Mbits (default)
Interfaces: 2 x D-sub plug, 9-pin, plug and socket with screening and vibration lock
Max. number of bytes fieldbus: 32 word input and 32 word output
Hardware diagnosis: status LEDs
Distributed clocks:
Type of connection: only remote bus
Current consumption power contacts:
Current consumption E-bus: typ. 450 mA
Special features: status LEDs
Weight: approx. 80 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/see documentation
Approvals: CE, UL, Ex