Article image EL4732

Beckhoff EL4732

EL4732 | 2-channel analog output terminal -10…+10 V with oversampling

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EL4732 analog output terminal generates signals in the range between -10 V and +10 V. The voltage is supplied to the process level with a resolution of 16 bits and is electrically isolated. The output channels have a common ground potential. The outputs are oversampled with an adjustable, integer multiple (oversampling factor: n) of the bus cycle time (n microcycles per bus cycle). For each microcycle, the EtherCAT Terminal receives a process data block that is output consecutively. The time base of the terminal can be synchronised precisely with other EtherCAT devices via distributed clocks. This procedure enables the temporal resolution of the analog output signals to be increased to n times the bus cycle time. In conjunction with the EL37xx (analog input terminal with oversampling), responses with equidistant time intervals, e.g. in the event of a threshold value being exceeded, become possible. The EL4732 device can output a maximum of 100,000 values (100 ksamples/s) per channel and second.

Technical parameters

Connection technology: 2-wire, single-ended
Number of outputs: 2
Power supply: via the E-bus
Signal voltage: -10…+10 V
Oversampling factor: n = 1…100 selectable
Distributed clocks: yes
Distributed clock precision: << 1 µs
Load: > 5 kΩ (short-circuit proof)
Output error: < 0.1 % (relative to end value)
Resolution: 16 bit (incl. sign)
Electrical isolation: 500 V (E-bus/signal voltage)
Conversion time: ~ 10 µs
Output rate: max. 100 ksamples/s
Current consumption power contacts:
Current consumption E-bus: typ. 180 mA
Bit width in the process image: n x 2 x 16 bit output, 32 bit CycleCounter
Special features: oversampling
Weight: approx. 50 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all ESxxxx terminals
Approvals: CE, UL, Ex, IECEx

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m