Article image EL2712

Beckhoff EL2712

EL2712 | 2-channel triac output terminal

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EL2712 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 1 A. The EtherCAT Terminal has two independent outputs and indicates its signal state by means of light emitting diodes.

Technical parameters

Connection technology: triac output, 2-wire
Number of outputs: 2 x make contacts
Rated load voltage: 12…230 V AC
Load type: ohmic, inductive
Distributed clocks:
Max. output current: 0.5 A per channel
Switching times: in zero crossing, 0.1…10 ms
Frequency range: 47…63 Hz
Surge voltage protection: > 275 V
Peak current: 40 A (16 ms), 1.5 A (30 s)
Standby current: 0.6 mA
Leakage current (OFF state): typ. 0.8 mA, max. 1.5 mA
Switch-on time: 0.1…10 ms, zero crossing
Switch-off time: T/2
Max. residual voltage: 1.5 V (60 mA…1 A), 150 Ω (< 60 mA)
Current consumption E-bus: typ. 120 mA
Electrical isolation: 500 V (E-bus/field voltage), 3750 V AC (1 min.)
Current consumption power contacts:
Bit width in the process image: 2 outputs
Configuration: no address or configuration setting
Special features: suitable for conventional blind motors
Weight: approx. 55 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all ESxxxx terminals

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m