Article image EL2622

Beckhoff EL2622

EL2622 | 2-channel relay output terminal 230 V AC, 5 A, potential-free make contacts, no power contacts

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EL2622 output terminal has two relays each of which has a single contact and can be generally used for switching devices requiring mains power. The EtherCAT Terminal indicates its signal state by means of light emitting diodes. The EL2622 has potential-free contacts. The power contacts are not looped through.

Technical parameters

Connection technology: relay output
Number of outputs: 2 x make contacts
Nominal voltage: 230 V AC/30 V DC
Load type: ohmic, inductive, lamp load
Distributed clocks:
Ohmic switching current: 5 A AC/DC per channel
Inductive switching current: 2 A AC/DC per channel
Minimum permitted load: 10 mA at 5 V DC
Lamp test, electronic ballast: 4 x 58 W
Current consumption E-bus: typ. 170 mA
Electrical isolation: 500 V (E-bus/field potential)
Current consumption power contacts:
Bit width in the process image: 2 outputs
Operating cycles mech. (min.): 2 x 107
Operating cycles electr. (min.): 1 x 105 (5 A/30 V DC)
Configuration: no address or configuration setting
Special features:
Weight: approx. 50 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all ESxxxx terminals
Approvals: CE, UL

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m