Article image EL2602

Beckhoff EL2602

EL2602 | 2-channel relay output terminal 230 V AC, 5 A, make contacts

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EL2602 output terminal has two relays each of which has a single contact. The relay contact is connected to the power contacts, which are suitable for use at up to 230 V AC, and can be generally used for switching devices requiring mains power. The EtherCAT Terminal indicates its signal state by means of light emitting diodes.

Technical parameters

Connection technology: relay output
Number of outputs: 2 x make contacts for power contact
Nominal voltage: 230 V AC/30 V DC
Load type: ohmic, inductive, lamp load
Distributed clocks:
Ohmic switching current: 5 A AC/DC per channel
Inductive switching current: 2 A AC/DC per channel
Minimum permitted load: 10 mA at 5 V DC
Lamp test, electronic ballast: 4 x 58 W
Current consumption E-bus: typ. 170 mA
Electrical isolation: 500 V (E-bus/field potential)
Current consumption power contacts: load-dependent
Bit width in the process image: 2 outputs
Operating cycles mech. (min.): 2 x 107
Operating cycles electr. (min.): 1 x 105 (5 A/30 V DC)
Configuration: no address or configuration setting
Special features: 1-wire connection possible
Weight: approx. 50 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all ESxxxx terminals
Approvals: CE, UL