Article image EL1512

Beckhoff EL1512

EL1512 | Up/down counter 24 V DC, 1 kHz

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EL1512 EtherCAT Terminal is an up/down counter. It transmits the counter state to the higher-level automation device in an electrically isolated manner. When it is used as a single-channel up/down counter (32 bit), the pulse is set via the clock input, while the count direction is set via the up/down input. The input can also be used as a gate input for triggering the counter. In two-counter mode, two separate counters (Clock and Clock1 inputs) are available, which can be parameterised as up or down counters. The signal state of the inputs is indicated by light emitting diodes. The EL1512 is particularly suitable for simple counting tasks, e.g. in connection with flow meters.

Technical parameters

Connection technology: 1 x up/down counter, 2 x up or down counter
Specification: EN 61131-2, type 1, “0”: < 5 V DC, “1”: > 15 V DC, typ. 5 mA
Number of counters: 1 or 2
Nominal voltage: 24 V DC (-15 %/+20 %)
“0” signal voltage: -3…+5 V (EN 61131-2, type 1)
“1” signal voltage: 15…30 V (EN 61131-2, type 1)
Input current: typ. 5 mA (EN 61131-2, type 1)
Counting frequency: max. 1 kHz
Distributed clocks:
Current consumption power contacts: typ. 14 mA + load
Current consumption E-bus: typ. 130 mA
Counter depth: 32 bit
Electrical isolation: 500 V (E-bus/field potential)
Configuration: no address setting, configuration via the EtherCAT master
Special features: set counters
Weight: approx. 50 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Pluggable wiring: for all ESxxxx terminals
Approvals: CE, UL, Ex

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m