Article image EK3100

Beckhoff EK3100

EK3100 | PROFIBUS Bus Coupler

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EK3100 Bus Coupler connects PROFIBUS networks to the EtherCAT Terminals (ELxxxx) as well as the EtherCAT Box modules (EPxxxx) and converts the telegrams from PROFIBUS to the E-bus signal representation. One station consists of an EK3100 and any number of EtherCAT Terminals. The coupler is connected to PROFIBUS via a 9-pin D-sub plug. In EtherCAT, the PROFIBUS coupler has at its disposal a lower-level, powerful and ultra-fast I/O system with a large selection of terminals. The coupler supports the PROFIBUS profile and fits seamlessly into PROFIBUS networks.

Technical parameters

Task within EtherCAT system: coupling of standard digital and analog EtherCAT Terminals and EtherCAT Box modules to PROFIBUS networks
Number of EtherCAT Terminals: depending on the process data size
Type/number of peripheral signals: depending on the process data size
Protocol: PROFIBUS DP
Data transfer rates: up to 12 Mbaud (automatic detection)
Configuration: not required
Bus interface: 1 x D-sub 9-pin socket with shielding
Power supply: 24 V DC (-15 %/+20 %)
Input current: typ. 120 mA + (total E-bus current)/4
Current consumption E-bus: up to 2 A
Power contacts: 24 V DC max./10 A max.
Electrical isolation: 500 V (power contact/supply voltage/Ethernet)
Dimensions (W x H x D): 64 mm x 100 mm x 73 mm
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Approvals: CE, UL, Ex

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m