Article image EJ3318

Beckhoff EJ3318

EJ3318 | 8-channel input thermocouple

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EJ3318 analog input allows the direct connection of eight thermocouples and is therefore particularly well suited to compact applications on the signal distribution board. The EtherCAT plug-in module's circuit can operate thermocouple sensors using the 2-wire technique. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The error LEDs indicate a broken wire. The compensation for the cold junction is done by two RTDs (PT1000), which can be placed anywhere on the signal distribution board. The EJ3318 can also be used for mV measurements.

Technical parameters

Technology: temperature measurement
Sensor types: thermocouples type K, J, L, E, T, N, U, B, R, S, C (default setting type K), mV measurement
Number of inputs: 8 x TC, 2 x PT1000 (compensation for the cold junction)
Connection method: 2-wire
Measuring range: in the range defined in each case for the sensor (default setting: type K; ‑200…+1370 °C); mV measurement: ±30 mV…±75 mV
Resolution: 0.1 °C per digit
Measuring error: < ±0.3 % (relative to full scale value)
Input filter limit frequency: typ. 1 kHz; depending on sensor length, conversion time, sensor type
Conversion time: approx. 5 s up to 40 ms, depending on configuration and filter setting, default: approx. 500 ms
Auxiliary power current:
Distributed clocks:
Power supply: via the E-bus
Wiring fail indication: yes
Current consumption E-bus: 190 mA
Electrical isolation: 500 V (E-bus/field potential)
Special features: open-circuit recognition, error recognition of the external cold junction compensation (CJC)
Dimensions (W x H x D): approx. 12 mm x 66 mm x 55 mm
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Approvals/markings: CE, UL

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m