QS3.241
DIN-rail power supplies for 1-phase systems
100-240V Wide-range input, active PFC. Efficiency up to 90%, SEMI-F47-200 approved. Negligibly low input inrush current. 50% Power reserves available up to 4s. Full output power between -25 and +60°C. Spring-clamp terminals
| AC-Input Voltage: | AC 100-240V (± 15%) |
| DC-Input Voltage: | DC 110V-300V (-20%/+25%) |
| EN61000-3-2(PFC-Norm): | fulfilled |
| Power Factor: | 0.47 |
| Input Inrush Current Limitation: | active |
| Peak turn on current: | 5A/10A (B1) |
| External Input Fuse Recommendation: | min. B-6A / C-6A |
| Nominal Voltage: | 24Vdc |
| Adjustment Range: | 24-28V |
| Output Current Range: | 3.4-3A |
| Output Current: | 3A at 28V 3.4A at 24V |
| Output Power: | 80W |
| Power Reserves: | 50% BonusPower® |
| max. Ripple and Noise Voltage: | 50mVpp |
| Size (WxHxD): | 32mm x 124mm x 102mm |
| Weight per Piece (excluding packing): | 440g |
| Operat. Temperature Range: | -25°C ... +70°C |
| Derating: | 2W/°C at >+60°C |
| Mounting Method: | DIN-Rail |
| Efficiency, typ.: | 90.0% |
| Power Losses, typ.: | 9.1W |
| MTBF SN 29500 @ 40°C (h): | 1.451.000h |
| Connection method: | Spring-clamp terminals |
| B1): | Peak current at 120Vac/230Vac, ambient temperature of +40°C and cold start |
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |