ML60.122
DIN-rail power supplies for 1-phase systems
100-240V Wide-range input. NEC Class2 compliant. Adjustable output voltage. Efficiency up to 87.6%. Low no-load losses and excellent partial-load efficiency. Compact design, width only 45mm. Electronic inrush current limitation. Operation down to -40°C. Full output power between -25°C and +60°C. Large international approval package
| AC-Input Voltage: | AC 100-240V (-15%/+10%) |
| DC-Input Voltage: | DC 110V-300V (-20%/+25%) |
| EN61000-3-2(PFC-Norm): | fulfilled |
| Power Factor: | 0.44 |
| Input Inrush Current Limitation: | active |
| Peak turn on current: | 6A/6A (C1) |
| External Input Fuse Recommendation: | min. B-6A / C-3A |
| Nominal Voltage: | 12Vdc |
| Adjustment Range: | 12-15V |
| Output Current Range: | 4.5-3.6A |
| Output Current: | 3.6A at 15V 4.5A at 12V |
| Output Power: | 54W |
| max. Ripple and Noise Voltage: | 50mVpp |
| Size (WxHxD): | 45mm x 75mm x 91mm |
| Weight per Piece (excluding packing): | 250g |
| Operat. Temperature Range: | -40°C ... +70°C |
| Derating: | 1.4W/°C at >+60°C |
| Mounting Method: | DIN-Rail |
| Efficiency, typ.: | 87.6% |
| Power Losses, typ.: | 7.6W |
| MTBF SN 29500 @ 40°C (h): | 1.571.000h |
| Connection method: | Screw terminals |
| C1): | between -40°C and +70°C |
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |