CP20.241-R1
Power supply with integrated decoupling function
AC 100-240V Wide-range input. Width only 48mm. Built-in decoupling mosfet for 1+1 and n+1 redundancy. Efficiency up to 95.2%. 20% Output power reserves. Safe Hiccup. PLUS, overload mode. Easy fuse breaking – 3 times nominal current for 12ms. Active power factor correction (PFC). Minimal inrush current surge. Full power between -40°C and +60°C. DC-OK relay contact. Current sharing feature included
| AC-Input Voltage: | AC 100-240V (-15%/+10%) | 
| DC-Input Voltage: | DC 110V-150V (± 20%) | 
| EN61000-3-2(PFC-Norm): | fulfilled | 
| Harmonic Correction: | active | 
| Power Factor: | 0.95 | 
| Input Inrush Current Limitation: | active | 
| Peak turn on current: | 10A/4.5A | 
| External Input Fuse Recommendation: | min. B - 10A / C - 10A | 
| Nominal Voltage: | 24Vdc | 
| Adjustment Range: | 24 | 
| Output Current Range: | 20A | 
| Output Current: | 20A at 24V | 
| Output Power: | 480W | 
| Power Reserves: | 20% Power Boost | 
| max. Ripple and Noise Voltage: | 50mVpp | 
| Size (WxHxD): | 48mm x 124mm x 127mm | 
| Weight per Piece (excluding packing): | 830g | 
| Operat. Temperature Range: | -40°C ... +70°C | 
| Derating: | 12W/°C at >60°C | 
| Mounting Method: | DIN-Rail | 
| Efficiency, typ.: | 95.2% | 
| Power Losses, typ.: | 24.2W | 
| MTBF SN 29500 @ 40°C (h): | 543.000h | 
| Connection method: | Hot-swap | 
| DC-OK Signal: | yes | 
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg | 
| Length: | 0.00 m | 
| Width: | 0.00 m | 
| Height: | 0.00 m |