Description

The device upgrades a conventional HART or 4 .. 20 mA field device with a WirelessHART interface. Installation in Zone 0, 20, Installation in Class I, II, Division 1, Installation in Class III, Installation in Class I, Division 2, Ex i circuits for Ex i field devices, Cast aluminum housing, Loop powered, Direct mounting on HART or 4 mA .. 20 mA field device, Encapsulated antenna, Up to 8 field devices in multidroppa. The supply is ensured via loop power. Due to its intrinsically safe circuits, the adapter can be mounted on an intrinsically safe field device or anywhere in the 4 .. 20 mA loop. Up to 8 HART field devices can be connected to each other in multidrop mode. The encapsulated antenna allows for use in harsh environments. The device can be programmed with a configuration tool easily (DTM or DD).

Technical parameters

Rated voltage: 7 ... 30 V DC
Rated current: < 1 mA , max. 25 mA
Output rated operating current: 3.2 ... 25 mA
Supply: loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V
Connection: - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point
HART communication: Protocol: HART 7.1, backward compatible
HART communication: Number of devices: up to 8 HART field devices (depending on installation)
Interface: internal antenna
Communication: WirelessHART specifications - physical layer: IEEE 802.15.4.2006 - frequency band: 2.4 GHz (ISM band, licence free) - maximum transmit power: +10 dBm - outdoor transmission range: 235 m - communication standard: WirelessHART
Radio and telecommunication terminal equipment: The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning.
HART communication: Directive 2014/53/EU: EN 300 328 V2.1.1:2016 EN 301 489-1 V2.2.0:2017 EN 301 489-17 V3.2.0:2017
HART communication: FCC CFR47 Part 15 B and C: ANSI C63.4-2003 , FCC ID: X89-WA1101
Degree of protection: IEC 60529:2013
Ambient temperature: temperature class T5: -40 ... 85 °C (-40 ... 185 °F) temperature class T6: -40 ... 75 °C (-40 ... 167 °F)
Storage temperature: -40 ... 85 °C (-40 ... 185 °F)
Relative humidity: max. 100 %
Degree of protection: IP67
Material: Aluminum alloy with polyurethane enamel paint
Mass: 460 g
Dimensions: 60.8 x 60.8 x 100 mm (l x w x h)
EU-Type Examination Certificate: FM 17 ATEX 0046 X
HART communication: Marking: II 1G Ex ia IIC T6...T5 Ga II 1D Ex ia IIIC T95°C Da
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012
FM approval: FM 17 NUS 0010 FM 17 US 0191 X
Directive conformity: Control drawing: 116-0425 (cFMus)
Directive conformity: Approved for: IS Class I, II, III, Division 1, Groups A-G Class I, Zone 0, AEx ia IIC T6...T5 Ga Zone 20, AEx ia IIIC T95°C Da
CSA approval: FM 17 NCA 0004 FM 17 CA 0102 X
Directive conformity: Control drawing: 116-0425 (cFMus)
Directive conformity: Approved for: IS Class I, II, III, Division 1, Groups A-G Ex ia IIC T6...T5 Ga Ex ia IIIC T95°C Da associated apparatus [Ex ia]
IECEx approval: IECEx certificate: IECEx FMG 17.0020X
IECEx approval: IECEx marking: Ex ia IIC T6...T5 Ga , Ex ia IIIC T95°C Da
IECEx approval: Standards: IEC 60079-0:2011 , IEC 60079-1:2014 , IEC 60079-11:2011 , IEC 60079-31:2013
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.