324436
KCD2-SLD-Ex1.1245
Solenoid Driver
This isolated barrier is used for intrinsic safety applications. 1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 12 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa. It supplies power to solenoids, LEDs and audible alarms located in a hazardous area. The device is controlled with a loop powered signal or a bus powered logic signal. The device is immune to the test pulses of various control systems. The device simulates a minimum load at the input. The minimum load can be activated and de-activated. The line fault transparency function can display a line fault in the field by a change in impedance at the switching input of the solenoid driver. A line fault is indicated by a red LED and output via the fault indication output or a switch contact.
Signal type: | Digital Output |
Safety Integrity Level (SIL): | SIL 3 |
Connection: | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered |
Rated voltage: | 19 ... 30 V DC loop powered |
Input current: | 75 mA at 24 V , 270 Ω load |
Power dissipation: | 1.3 W at 24 V , 270 Ω load |
Connection side: | control side |
Connection: | terminals 5+, 6- |
Test pulse length: | max. 2 ms from DO card |
Signal level: | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC |
Rated current: | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
Inrush current: | < 200 mA , 10 ms loop powered |
Connection side: | field side |
Connection: | terminals 1+, 2- |
Internal resistor: | 240 Ω |
Current: | typ. 45 mA |
Voltage: | typ. 12 V |
Current limit: | 50 mA |
Open loop voltage: | typ. 24.6 V |
Load: | nominal 0.05 ... 18 kΩ |
Output II: | fault signal |
: Connection: | terminals 7, 8 , non-intrinsically safe |
: Contact loading: | 30 V DC/ 0.5 A resistive load |
: Mechanical life: | 105 switching cycles |
: Energized/De-energized delay: | ≤ 20 ms / ≤ 20 ms |
Line fault detection: | signal at short-circuit RB < 25 Ω, lead breakage RB > 50 kΩ ; test current < 500 µA |
Output/other circuits: | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output II/power supply: | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff |
Display elements: | LEDs |
Control elements: | DIP-switch |
Configuration: | via DIP switches |
Labeling: | space for labeling at the front |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
Electromagnetic compatibility: | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. |
Degree of protection: | IEC 60529:2013 |
Protection against electrical shock: | EN 61010-1:2010 |
Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection: | IP20 |
Connection: | screw terminals |
Mass: | approx. 150 g |
Dimensions: | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 |
Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
EU-Type Examination Certificate: | EXA 17 ATEX 0002 X |
Electromagnetic compatibility: Marking: | II 3(1)G Ex nC ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
Electromagnetic compatibility: Output I: | Ex ia |
Electromagnetic compatibility: Voltage: | 26 V |
Electromagnetic compatibility: Current: | 110 mA |
Electromagnetic compatibility: Power: | 715 mW |
Supply: Maximum safe voltage: | 60 V (Attention! The rated voltage can be lower.) |
Input: Maximum safe voltage: | 60 V (Attention! The rated voltage can be lower.) |
Collective error message: Maximum safe voltage: | 60 V (Attention! The rated voltage can be lower.) |
Galvanic isolation: Output I/other circuits: | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms |
Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010 |
UL approval: | E106378 |
Directive conformity: Control drawing: | 116-0448 (cULus) |
IECEx approval: IECEx certificate: | IECEx EXA 17.0001X |
IECEx approval: IECEx marking: | Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Optional accessories: | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
ECCN: | |
Country of Origin: | SG |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |