306126
NJ2-11-N-G
Inductive sensor
Series: Cylindrical type, Housing material: Stainless steel 1.4305 / AISI 303, Output type: 2-wire, Installation: flush, Type of voltage: DC, Connection type: cable PVC , 2 m, Degree of protection: IP68fa
| Switching function: | Normally closed (NC) |
| Output type: | NAMUR |
| Rated operating distance: | 2 mm |
| Installation: | flush |
| Assured operating distance: | 0 ... 1.62 mm |
| Actual operating distance: | 1.8 ... 2.2 mm |
| Reduction factor rAl: | 0.4 |
| Reduction factor rCu: | 0.3 |
| Reduction factor r304: | 0.85 |
| Output type: | 2-wire |
| Nominal voltage: | 8.2 V (Ri approx. 1 kΩ) |
| Switching frequency: | 0 ... 3000 Hz |
| Hysteresis: | 0.5 ... 3.5 typ. 2 % |
| Current consumption: Measuring plate not detected: | min. 3 mA |
| Current consumption: Measuring plate detected: | ≤ 1 mA |
| Safety Integrity Level (SIL): | SIL 2 |
| MTTFd: | 5887 a |
| Mission Time (TM): | 20 a |
| Diagnostic Coverage (DC): | 0 % |
| Standard conformity: NAMUR: | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Standard conformity: Standards: | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
| EAC conformity: | TR CU 012/2011 |
| FM approval: Control drawing: | 116-0165 |
| UL approval: Ordinary Location: | E87056 |
| UL approval: Hazardous Location: | E501628 |
| UL approval: Control drawing: | 116-0452 |
| CCC approval: | CCC approval / marking not required for products rated ≤36 V |
| Ambient temperature: | -25 ... 100 °C (-13 ... 212 °F) |
| Connection type: | cable PVC , 2 m |
| Core cross-section: | 0.34 mm2 |
| Housing material: | Stainless steel 1.4305 / AISI 303 |
| Sensing face: | PVDF |
| Degree of protection: | IP68 |
| Cable: Bending radius: | > 10 x cable diameter |
| Use in the hazardous area: | see instruction manuals |
| ECCN: | |
| Country of Origin: | ID |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |