278766
HiD2872
Solenoid Driver
This isolated barrier is used for intrinsic safety applications. 2-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 40 mA at 12 V DC, 55 mA current limit, Contact or logic control input, Entity parameter Io/Isc = 110 mA, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508 (bus powered), Up to SIL 3 acc. to IEC 61508 (loop powered)pa. It supplies power to solenoids, LEDs, and audible alarms, located in a hazardous area. It is controlled with a loop-powered control signal, switch contact, transistor, or logic signal. At full load, 12 V at 40 mA (with 55 mA current limit) is available for the hazardous area application. An alternative low current output is available for driving a single LED without installing an external current limiting resistor. Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. This device mounts on a HiD Termination Board.
| Signal type: | Digital Output |
| Safety Integrity Level (SIL): | SIL 3 |
| Connection: | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage: | 20.4 ... 30 V DC loop powered 20.4 ... 30 V DC bus powered via Termination Board |
| Input current: | 62 mA at 24 V, 300 Ω load (per channel) |
| Power dissipation: | 1 W at 24 V, 300 Ω load (per channel) |
| Connection side: | control side |
| Connection: | SL1: 8a(+), 7a(-); 10a(+), 9a(-) bus powered SL1: 8b(+), 7b(-); 9b(+), 10b(-) loop powered |
| Control input: | external switch (dry contact or open collector) non isolated or logic signal input fully floating |
| Signal level: | 1-signal: 15...30 V DC (current limited at 3 mA) or contact close (internal 10 kΩ pull-up) 0-signal: 0...5 V DC or contact open |
| Power dissipation: | 1 W at 24 V, 300 Ω load (per channel) for loop powered |
| Inrush current: | 0.2 A , 15 ms loop powered |
| Connection side: | field side |
| Connection: | SL2: 5a(+), 5b(-), 7a(+); 1a(+), 1b(-), 3b(+) |
| Internal resistor: | approx. 240 Ω |
| Current: | ≤ 40 mA |
| Voltage: | ≥ 12 V |
| Current limit: | 55 mA |
| Open loop voltage: | approx. 22.5 V |
| Load: | nominal 0.1 ... 5 kΩ |
| Switching frequency: | - bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz - loop powered: max. 10 Hz |
| Energized/De-energized delay: | - bus powered: filter OFF: 1 ms, filter ON: 10 ms - loop powered: switch-on 50 ms, switch-off 6 ms (300 Ω load) |
| Connection: | SL1: 6b |
| Output type: | open collector transistor (internal fault bus) |
| Fault current: | 4 mA pulsing (20 ms ON, 200 ms OFF) |
| Fault level: | lead short-circuit detection at < 25 Ω lead breakage detection at > 100 kΩ typical |
| Output/Output: | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V |
| Output/power supply, inputs, and collective error: | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 For further information see system description. |
| Degree of protection: | IEC 60529:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Relative humidity: | 5 ... 90 %, non-condensing up to 35 °C (95 °F) |
| Degree of protection: | IP20 |
| Mass: | approx. 140 g |
| Dimensions: | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
| Mounting: | on Termination Board |
| Coding: | pin 1 and 4 trimmed For further information see system description. |
| EU-Type Examination Certificate: | CESI 10 ATEX 036 |
| Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Electromagnetic compatibility: Output: | Ex ia Ga, Ex ia Da, Ex ia Ma |
| Electromagnetic compatibility: Voltage: | 26 V |
| Electromagnetic compatibility: Current: | 110 mA |
| Electromagnetic compatibility: Power: | 715 mW |
| Supply: Maximum safe voltage: | 253 V AC (Attention! Um is no rated voltage.) |
| Certificate: | PF 10 CERT 1729 X |
| Supply: Marking: | II 3G Ex nA IIC T4 Gc |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| CSA approval: Control drawing: | 366-005CS-12B (cCSAus) |
| IECEx approval: | IECEx CES 10.0013 |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Country of Origin: | SG |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |