Pepperl+Fuchs 272953

HIC2027DE

SMART Transmitter Power Supply

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA .. 20 mA or 0/1 V .. 5 V, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. The device supplies 2-wire transmitters in the hazardous area, and can also be used with current sources. It transfers the analog input signal to the safe area as two isolated output signals. Bi-directional communication is supported for SMART transmitters that use current modulation to transmit data and voltage modulation to receive data. The output is selected as a current source, current sink, or voltage source via switches. This device mounts on a HiC Termination Board.

Technical parameters

Signal type: Analog input
Safety Integrity Level (SIL): SIL 2
Connection: SL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage: 18 ... 30 V DC bus powered via Termination Board
Ripple: within the supply tolerance
Power dissipation: approx. 1.4 W at 20 mA transfer current, 250 Ω in both outputs
Power consumption: 2 W
Connection side: field side
Connection: SL2: 5a(+), 5b(-): sink SL2: 1a(+), 1b(-), 7a(-): source
Input signal: 0/4 ... 20 mA
Voltage drop: SL2: 1a(+), 1b(-), 7a(-): ≤ 6.1 V at 20 mA
Short-circuit current: SL2: 5a(+), 5b(-): 25 mA , wake up pulse: 36 mA, 20 ms (Honeywell DE)
Input resistance: SL2: 5a(+), 5b(-): max. 500 Ω (BRAIN) (250 Ω load)
Available voltage: SL2: 5a(+), 5b(-): ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA
Connection side: control side
Connection: SL1: 8a(+), 7a(-), channel 1: source and sink SL1: 10a(+), 9a(-), channel 2: source and sink
Load: channel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V) channel 2: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)
Output signal: 0/4 ... 20 mA or 0/1 ... 5 V
Ripple: max. 50 µA rms
Deviation: Iout < 20 µA (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V
: Influence of ambient temperature: current output: 0.25 µA/K voltage output: 80 µV/K
Frequency range: field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB) [DE 1 kHz (-3 dB)]
Settling time: 6 ms
Rise time/fall time: 2 ms
Output/power supply: functional insulation, rated insulation voltage 50 V AC
Output/Output: functional insulation, rated insulation voltage 50 V AC
Display elements: LED
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2012 EN 61326-3-2:2008
Degree of protection: IEC 60529:2001
Protection against electrical shock: UL 61010-1:2012
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Mass: approx. 100 g
Dimensions: 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch)
Mounting: on Termination Board
Coding: pin 2 and 3 trimmed For further information see system description.
EU-type examination certificate: BASEEFA 13 ATEX 0075 X
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Input: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supply: Maximum safe voltage: 250 V (Attention! The rated voltage can be lower.)
Equipment: terminals 5a, 5b
Supply: Voltage Uo: 25.2 V
Supply: Voltage Uq: 28.2 V
Supply: Current Io: 93 mA
Supply: Power Po: 656 mW
Supply: Internal capacitance Ci: 12 nF
Supply: Internal inductance Li: 0 mH
Equipment: terminals 1a, 1b, 7a
Supply: Voltage Ui: 30 V
Supply: Current Ii: 115 mA
Supply: Power Pi: 700 mW
Supply: Voltage Uo: 5 V
Supply: Current Io: 6.8 mA
Supply: Power Po: 1.6 mW
Output: Maximum safe voltage: 250 V (Attention! The rated voltage can be lower.)
Certificate: BASEEFA 13 ATEX 0076 X
Output: Marking: II 3G Ex nA II T4 Gc [device in zone 2]
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
UL approval: Control drawing: 116-0349 (cULus)
IECEx approval: IECEx BAS 13.0042X
UL approval: Approved for: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Note: Both output loads must be connected to ensure complete and correct operation within the technical specification.
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: Singapur
EAN: 4050143075867
Weight: 0.14 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m