Pepperl+Fuchs 254835

LB6111ER

Digital Output with Shutdown Input

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The digital output features 4 independent channels. 4-channel, Outputs Ex ia, Installation in Zone 2 or safe area, Line fault detection (LFD)pa. The device can be used to drive solenoids, sounders, or LEDs. Open and short-circuit line faults are detected. The outputs are galvanically isolated from the bus and the power supply. The output can be switched off via a contact. This can be used for bus-independent safety applications.

Technical parameters

Occupied slots: 2
Safety Integrity Level (SIL): SIL 2
Connection: backplane bus / booster terminals
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Input voltage range: 18.5 ... 32 V DC (SELV/PELV) booster voltage
Power dissipation: 3 W
Power consumption: 0.15 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 4
Suitable field devices: Field device: Solenoid Valve
Suitable field devices: Field device [2]: audible alarm
Suitable field devices: Field device [3]: visual alarm
Connection: channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-
Current limit: 40 mA
Internal resistor: max. 320 Ω
Open loop voltage: 24.5 V
Line fault detection: can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms)
Suitable field devices: Short-circuit: < 100 Ω
Suitable field devices: Open-circuit: > 15 kΩ
Response time: 10 ms (depending on bus cycle time)
Watchdog: within 0.5 s the device goes in safe state, e.g. after loss of communication
Reaction time: 10 s
LED indication: Power LED (P) green: supply Status LED (I) red: line fault , red flashing: communication error
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 when mounted on backplane
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 150 g
Dimensions: 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
EU-type examination certificate: PTB 03 ATEX 2042 X
Electromagnetic compatibility: Marking: II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC
Output: Voltage: 27.8 V
Output: Current: 107 mA
Output: Power: 744 mW
Output: Internal capacitance: 1.65 nF
Output: Internal inductance: 0 mH
Certificate: PF 08 CERT 1234 X
Output: Marking: II 3 G Ex nA IIC T4 Gc
Galvanic isolation: Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006
ATEX approval: PTB 03 ATEX 2042 X
IECEx approval: BVS 09.0037X
Directive conformity: Approved for: Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC
Marine approval: Lloyd Register: 15/20021
Marine approval: DNV GL Marine: TAA0000034
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: Deutschland
EAN: 4050143064120
Weight: 0.18 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m