248763
KFD2-UT2-2-1
Universal Temperature Converter
This signal conditioner provides the galvanic isolation between field circuits and control circuits. 2-channel signal conditioner, 24 V DC supply (Power Rail), Thermocouple, RTD, potentiometer or voltage input, Usable as signal splitter (1 input and 2 outputs), Voltage output 0/1 V .. 5 V, Configurable by PACTware, Line fault (LFD) and sensor burnout detection, Up to SIL 2 acc. to IEC 61508/IEC 61511pa. The device converts the signal of a resistance thermometer, thermocouple, or potentiometer to a proportional output voltage. The device can also be configured as a signal splitter. The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output. The device is easily configured by the use of the PACTware configuration software. For additional information, refer to the manual and www.pepperl-fuchs.com.
Signal type: | Analog input |
Safety Integrity Level (SIL): | SIL 2 |
Connection: | terminals 14+, 15- or power feed module/Power Rail |
Rated voltage: | 20 ... 30 V DC |
Ripple: | within the supply tolerance |
Power dissipation/power consumption: | ≤ 0.8 W / 0.8 W |
Programming interface: | programming socket |
Connection side: | field side |
Connection: | terminals 1, 2, 3; 4, 5, 6 |
RTD: | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
: Measuring current: | approx. 200 µA with RTD |
: Types of measuring: | 2-, 3-wire connection |
: Lead resistance: | max. 50 Ω per line |
: Measurement loop monitoring: | sensor breakage, sensor short-circuit |
Thermocouples: | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |
: Cold junction compensation: | external and internal |
: Measurement loop monitoring: | sensor breakage |
Potentiometer: | 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection) |
Voltage: | selectable within the range -100 ... 100 mV |
Input resistance: | ≥ 1 MΩ (-100 ... 100 mV) |
Connection side: | control side |
Voltage output: | 0 ... 5 V or 1 ... 5 V ; output resistance: ≤ 5 Ω ; load: ≥ 10 kΩ |
Connection: | output I: terminals 7-, 8+ output II: terminals 10-, 11+ |
Fault signal: | downscale 0 V or 0.5 V, upscale 5.375 V |
Deviation: After calibration: | Pt100: ± (0.06 % of measurement value in K + 0.1 K (4-wire connection)) thermocouple: ± (0.05 % of measurement value in °C + 1 K (1.2 K for types R and S)) this includes ± 0.8 K error of the cold junction compensation mV: ± 50 µV potentiometer: ± 0.05 % of full scale, (excludes errors due to lead resistance) output: 1 to 5 V output: ± 4 mV from 0 to 103.1 % of span; 0 to 5 V output: ± 4 mV from 0.3 to 102.5 % of span |
Deviation: Influence of ambient temperature: | deviation of CJC included: Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*) thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*) mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔTamb*) potentiometer: ± 0.006 % of span/K ΔTamb*) *) ΔTamb = ambient temperature change referenced to 23 °C (296 K) |
Deviation: Influence of supply voltage: | < 0.01 % of span |
Reaction time: | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s |
Input/Other circuits: | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff |
Output/supply, programming input: | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
Display elements: | LEDs |
Configuration: | via PACTware |
Labeling: | space for labeling at the front |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
Electromagnetic compatibility: | NE 21:2006 |
Degree of protection: | IEC 60529:2001 |
Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection: | IP20 |
Connection: | screw terminals |
Mass: | approx. 130 g |
Dimensions: | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Optional accessories: | - FDT framework PACTware 5.X - device type manager DTM Interface Technology - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) |
ECCN: | |
Country of Origin: | Singapur |
EAN: | 4050143074617 |
Weight: | 0.15 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |