236170
HICTB08-YC3-RRB-KS-CC-AM08
Termination Board
System board for Yokogawa CENTUM VP, For 8-channel AI card AAI135, For 8-channel AI/AO card AAI835, For 8 modules, Recommended modules: HiC2025 (AI), HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Safe area: Yokogawa system connector, 40-pinpa. The function of the Termination Board as well as the connector pin assignment exactly fit the requirement of Yokogawa systems. Information about missing supply voltage of the interface modules is available for the system as potential-free contact. Wiring errors from field will be reported via the same relay contact if the interface module supports this function. The Termination Boards are supplied with a robust glass fiber reinforced plastic housing as standard. This design permits the fast and reliable installation on 35 mm DIN mounting rail acc. to EN 60715 in the cabinet.
Nominal voltage: | 24 V DC , in consideration of rated voltage of used isolators |
Voltage drop: | 0.9 V , voltage drop across the series diode on the termination board must be considered |
Ripple: | ≤ 10 % |
Fusing: | 2 A , in each case for 8 modules |
Power dissipation: | ≤ 500 mW , without modules |
Reverse polarity protection: | yes |
Supply: | Redundancy available. The supply for the isolators is decoupled, monitored and fused. |
Output type: | volt-free contact |
Contact loading: | 30 V DC , 1 A |
Display elements: | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
Electromagnetic compatibility: | NE 21:2012 For further information see system description. |
Degree of protection: | IEC 60529:2001 |
Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature: | -40 ... 70 °C (-40 ... 158 °F) |
Degree of protection: | IP20 |
Connection: Field side: | explosion hazardous area: spring terminals , blue |
Connection: Control side: | non-explosion hazardous area: Yokogawa system connector, 40-pin |
Connection: Supply: | pluggable screw terminals , black |
Connection: Fault output: | pluggable screw terminals , black |
Core cross-section: | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 |
Material: | housing: polycarbonate |
Mass: | approx. 490 g |
Dimensions: | 205 x 175 x 153 mm (8.1 x 6.9 x 6.02 inch) , height including module assembly |
Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
EU-Type Examination Certificate: | CESI 06 ATEX 022 |
Connection: Marking: | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
Safe area: Maximum safe voltage: | 250 V (Attention! Um is no rated voltage.) |
Galvanic isolation: Field circuit/control circuit: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 |
IECEx approval: | IECEx CES 06.0003 |
Directive conformity: Approved for: | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
ECCN: | |
Country of Origin: | Singapur |
EAN: | 4050143062850 |
Weight: | 0.90 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |