Series: Double sensor, Housing material: PC (glass-fiber-reinforced Makrolon), Output type: 2-wire, Installation: flush mountable, Type of voltage: DC, Connection type: screw terminals, Degree of protection: IP66 / IP68 / IP69fa

Technical parameters

Switching function: 2 x normally closed (NC)
Output type: NAMUR
Rated operating distance: 3 mm
Installation: flush mountable
Assured operating distance: 0 ... 2.4 mm For assured operating distance sar see Manual Functional Safety.
Actual operating distance: 2.7 ... 3.3 mm typ.
Actuating element: Stainless steel 1.4305 / AISI 303 8.5 mm x 8.5 mm x 0.5 mm
Reduction factor rAl: 0.4
Reduction factor rCu: 0.4
Reduction factor r304: 0.7
Reduction factor rSt37: 1
Reduction factor rBrass: 0.5
Output type: 2-wire
Nominal voltage: 8 V
Switching frequency: 0 ... 3 kHz
Hysteresis: typ. 5 %
Reverse polarity protection: reverse polarity protected
Short-circuit protection: yes
Suitable for 2:1 technology: yes , Reverse polarity protection diode not required
Current consumption: Measuring plate not detected: ≥ 3 mA
Current consumption: Measuring plate detected: ≤ 1 mA
Time delay before availability: ≤ 1 ms
Switching state indicator: LED, yellow
Valve status indicator: LED, yellow
Safety Integrity Level (SIL): SIL 2
MTTFd: 1730 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
Voltage: max. 32 V DC
Current: max. 240 mA
Short-circuit protection: no
Reverse polarity protection: yes, with reversed output LED is out of function, therfore more power for solenoid valve
Standard conformity: NAMUR: EN 60947-5-6:2000 IEC 60947-5-6:1999
Standard conformity: Electromagnetic compatibility: NE 21:2007
Standard conformity: Standards: EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
UL approval: cULus Listed, General Purpose, Class 2 Power Source
Standard conformity: Ordinary Location: E87056
Standard conformity: Hazardous Location: E501628
Standard conformity: Control drawing: 116-0455
CCC approval: CCC approval / marking not required for products rated ≤36 V
Ambient temperature: -40 ... 100 °C (-40 ... 212 °F)
Storage temperature: -40 ... 100 °C (-40 ... 212 °F)
Connection type: screw terminals
Connection (system side): Screw terminals, tightening torque min. 0.5 Nm Stripped length 7 mm , 1/2" NPT cable gland , usable thread length 13.5 mm , screw-in depth max. 13.5 mm
Core cross-section (system side): rigid: 0.14 ... 2.5 mm2 flexible: 0.14 ... 1.5 mm2 flexible with core-end sleeve: 0.25 ... 1.5 mm2
Connection (valve side): like connection (system side)
Core cross-section (valve side): like core cross section (system side)
Housing material: PC (glass-fiber-reinforced Makrolon)
Housing base: powder coated aluminum
Degree of protection: IP66 / IP68 / IP69
Tightening torque, housing screws: ≤ 2 Nm
Tightening torque, cable gland: Refer to NEC (National Electrical Code), hand-tight then wrench tightened (max. 3 turns)
Note: LED switch-off
Use in the hazardous area: see instruction manuals

Logistic parameters

ECCN:
Country of Origin: CZ
EAN: