217229
WHA-GW-F2D2-0-AS-Z2-ETH
WirelessHART-Gateway WHA-GW-F2D2-0-AS-Z2-ETH
The WirelessHART Gateway is the interface between the WirelessHART network and the control system or asset management system. The device supports WirelessHART networks with up to 250 network participants and provides a RS485 interface as well as an Ethernet interface. Both interfaces transmit the HART or MODBUS protocol. OPC connectivity can be realized via the HART OPC server. The device can be configured via the DTM or DD in connection with a configuration software. Furthermore, it provides a web interface for direct access via a web browser.
Rated voltage: | 20 ... 30 V DC SELV/PELV |
Power consumption: | < 5 W |
Connection: | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) |
Interface 1: | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation |
: Protocol: | HART UDP, MODBUS TCP |
: Cable length: | max. 100 m , depending on cables and transfer rate |
: Connection: | UTP, STP or FTP |
Interface 2: | RS-485 |
: Protocol: | HART, MODBUS RTU |
: Daisy-chain capability: | supported by duplicated connection terminals |
: Transfer rate: | max. 115 kBit/s |
: Cable length: | max. 1200 m , depending on cables and transfer rate |
: Bus termination: | integrated termination resistor , adjustable via DIP switch and software |
Interface: | omnidirectional dipole antenna, removable |
Communication: | WirelessHART specifications - physical layer: IEEE 802.15.4.2006 - frequency band: 2.4 GHz (ISM band, licence free) - transmission rate: 250 kBit/s - maximum transmit power: +10 dBm (EIRP) - transmission range: outdoor 250 m, indoor 50 m (under reference conditions) - communication standard: WirelessHART acc. to IEC 62591 |
Interface/power supply: | basic insulation according to IEC 61140, rated insulation voltage 50 Veff |
Interface/interface: | basic insulation according to IEC 61140, rated insulation voltage 50 Veff |
Display elements: | LED PWR (power supply status), one green LED LED COM (communication status), three yellow LEDs LED FLT (fault signal), one red LED |
Control elements: | 2 push buttons: - restore HART configuration - restore communication configuration DIP switches: - baud rate - RS-485 address - RS-485 termination - security mode |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 |
Radio and telecommunication terminal equipment: | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. |
Electromagnetic compatibility: Directive 2014/53/EU: | EN 300328: V2.1.1 EN 301489-17: V1.3.2 |
Electromagnetic compatibility: FCC CFR47 Part 15 B and C: | ANSI C63.4-2003 , FCC ID: SJC-M2140 |
Degree of protection: | IEC 60529 |
Shock resistance: | EN 60068-2-27 |
Vibration resistance: | EN 60068-2-6 |
Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature: | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity: | 5 ... 95 %, noncondensing |
Corrosion resistance: | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 |
Degree of protection: | IP66/IP67 |
Mass: | approx. 1 kg |
Dimensions: | 258 mm x 114 mm x 84 mm without antenna and cable glands |
Mounting: | wall mounting |
EU-type examination certificate: | FM 12 ATEX 0061 |
Electromagnetic compatibility: Marking: | II 3 G Ex nA nC IIC T4 Gc |
Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
FM approval: | Coc3042646 |
Directive conformity: Approved for: | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G |
IECEx approval: | IECEx FMG 12.0002 |
Directive conformity: Approved for: | Ex nA nC IIC T4 Gc , Ex nAc nCc T4 |
Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.00 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |