Pepperl+Fuchs 203355

KFD2-SR2-Ex2.W

Switch Amplifier

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. 2-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC 61508/IEC 61511pa. The proximity sensor or switch controls a change-over relay contact for the load in the non-explosion hazardous area. The normal output state can be reversed using switches S1 and S2. Switch S3 is used to enable or disable line fault detection of the field circuit. During an error condition, the relays revert to their de-energized state and the LEDs indicate the fault according to NAMUR NE44. A unique collective error messaging feature is available when used with the Power Rail system.

Technical parameters

Signal type: Digital Input
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 14+, 15-
Rated voltage: 19 ... 30 V DC
Ripple: ≤ 10 %
Rated current: ≤ 50 mA
Power dissipation: ≤ 1 W
Power consumption: ≤ 1 W
Connection side: field side
Connection: terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values: acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current: approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis: 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection: breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio: min. 20 ms / min. 20 ms
Connection side: control side
Connection: output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I, II: signal, relay
Contact loading: 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load
Minimum switch current: 2 mA / 24 V DC
Energized/De-energized delay: approx. 20 ms / approx. 20 ms
Mechanical life: 107 switching cycles
Collective error message: Power Rail
Switching frequency: ≤ 10 Hz
Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Low voltage: Directive 2014/35/EU: EN 61010-1:2010
Electromagnetic compatibility: NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018
Degree of protection: IEC 60529:1989+A1:1999+A2:2013
Functional safety: IEC/EN 61508:2010
Input: EN 60947-5-6:2000
Ambient temperature: -20 ... 70 °C (-4 ... 158 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: PTB 00 ATEX 2080
Low voltage: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Low voltage: Input: Ex ia
Low voltage: Voltage: 10.5 V
Low voltage: Current: 13 mA
Low voltage: Power: 34 mW (linear characteristic)
Supply: Maximum safe voltage: 253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Output: Maximum safe voltage: 253 V AC (Attention! The rated voltage can be lower.)
Fault indication output: Maximum safe voltage: 40 V DC (Attention! Um is no rated voltage.)
Certificate: PF 08 CERT 0803
Fault indication output: Marking: II (3)G [Ex ic Gc] IIC
Input: Ex ic
Fault indication output: Voltage: 10.5 V
Fault indication output: Current: 13 mA
Fault indication output: Power: 34 mW (linear characteristic)
Certificate: TÜV 99 ATEX 1493 X
Fault indication output: Marking: II 3G Ex ec nC IIC T4 Gc
Output: Contact loading: 50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
FM approval: FM certificate: FM19US0207X
FM approval: Control drawing: 116-0035
UL approval: E106378
FM approval: Control drawing: 116-0473 (cULus)
FM approval: Contact loading: 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load
FM approval: Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
IECEx approval: IECEx certificate: IECEx PTB 11.0034 , IECEx TUN 19.0013X
IECEx approval: IECEx marking: [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: ID
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m