Pepperl+Fuchs 188869

MB-FB-4R.HO.SC

High-Density Fieldbus Power Hub, Motherboard for Honeywell C-Series

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The FieldConnex. Universal Power Hub is a modular fieldbus power supply, providing the most options for most reliable communication. It supports explosion protection e.g. the High-Power Trunk for longest cable run and highest device count. The Power Hub supports optional Advanced Diagnostics for fast fieldbus commissioning and online monitoring. 4 segments, redundant, individual modules per segment, Customized for Honeywell, C-Series, High-power trunk: Live work on devices in any hazardous area, Optimized for size and quality, low heat dissipation, For FOUNDATION Fieldbus H1pa. The motherboard is the mounting plate for installation in the Honeywell C-channel. It connects to existing bulk power, communication and fault indication. Sockets for all modules enable simple installation and replacement without tools. For power redundancy with seamless transfer, pairs of modules feed each segment. Availability and a long service life are achieved through: only one passive impedance filter per segment with CREST for superior signal transmission, optimized design for low power dissipation and high-availability fieldbus termination. Any mounting direction allows optimized and space-saving cabinet layout.

Technical parameters

Design / Mounting: Motherboard based
Connection: Channel or external supply
Rated voltage: 19.2 ... 35 V SELV/PELV
Rated current: 6.3 A
Power dissipation: typ. 0.2 W per segment
Number of segments: Redundant: 4
Host-side: Honeywell Series C 300 System Connector
Terminating resistor: integrated 100 Ω
Fault signal: to Honeywell C 300 System
Fieldbus segment/Fieldbus segment: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Fieldbus segment/Supply: functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Electromagnetic compatibility: Directive 2004/108/EC: EN 61326-1:2006
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529
Fieldbus standard: IEC 61158-2
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Ambient temperature: -40 ... 60 °C (-40 ... 140 °F)
Storage temperature: -40 ... 85 °C (-40 ... 185 °F)
Relative humidity: < 95 % non-condensing
Shock resistance: 15 g , 11 ms
Vibration resistance: 1 g , 10 ... 150 Hz
Connection type: Honeywell channel or plug with screw flange
Core cross-section: 2.5 mm2 if supplied via plug with screw flange
Housing width: 150 mm
Housing height: 146 mm
Housing depth: 75 mm
Degree of protection: IP00
Mass: approx. 720 g
Mounting: Honeywell channel
FM approval: FM certificate: FM 19 US 0015 X and FM 19 CA 0011 X
FM approval: FM marking: AEx/Ex ec IIC T4
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Logistic parameters

ECCN:
Country of Origin: Singapur
EAN: 4050143060634
Weight: 0.85 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m