2-channel isolated barrier, 24 V DC supply (loop powered), Current input/output 4 mA .. 20 mA, transmitter power supply, Accuracy 0.1 %, Reverse polarity protection, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the field / to the control systempa. This isolated barrier is used for intrinsic safety applications. The device can be used as a repeater or transmitter power supply for 2-wire transmitters. This device is loop powered. No additional power supply has to be connected. Use the technical data to verify that proper voltage is available to the field devices.
| Signal type: | Analog input/analog output |
| Safety Integrity Level (SIL): | SIL 2 |
| Rated voltage: | loop powered |
| Connection: | terminals 12-, 11+; 8-, 10-, 9+ |
| Voltage: | 5 ... 35 V DC |
| Current: | 4 ... 20 mA |
| Power dissipation: | at 20 mA and Uin < 24.3 V: < 250 mW per channel at 20 mA and Uin > 24.3 V: < 500 mW per channel |
| Connection: | terminals 1+, 2-; 4+, 5- |
| Voltage: | for 5V < Uin < 24.3V: ≥ 0.9 x Uin - (0.37 x current in mA) - 1.0 for Uin > 24.3 V: ≥ 21 V - (0.36 x current in mA) |
| Short-circuit current: | at Uin > 24.3 V : ≤ 65 mA |
| Transfer current: | ≤ 40 mA |
| Accuracy: | 0.1 % |
| Deviation: After calibration: | ≤ ± 20 µA; incl. calibration, linearity, hysteresis and load fluctuations at the field side up to a load of 1 kΩ at 20 °C (68 °F) |
| Deviation: Influence of ambient temperature: | ≤ ± 2 µA/K at Uin ≤ 20 V; ≤ ± 5 µA/K at Uin > 20 V |
| Rise time: | ≤ 5 ms at bounce from 4 ... 20 mA and Uin < 24 V |
| Field circuit/control circuit: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2012 EN 61326-3-2:2008 |
| Degree of protection: | IEC 60529:2001 |
| Protection against electrical shock: | UL 61010-1:2012 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 100 g |
| Dimensions: | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate: | BAS 98 ATEX 7343 X |
| Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) |
| Electromagnetic compatibility: Voltage: | 25.2 V |
| Electromagnetic compatibility: Current: | 93 mA |
| Electromagnetic compatibility: Power: | 585 mW |
| Control circuit: Maximum safe voltage: | 250 V eff (Attention! The rated voltage can be lower.) |
| Field circuit: Maximum safe voltage: | 250 V eff (Attention! The rated voltage can be lower.) |
| Certificate: | TÜV 99 ATEX 1499 X |
| Field circuit: Marking: | II 3G Ex nA II T4 [device in zone 2] |
| Galvanic isolation: Field circuit/control circuit: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| FM approval: Control drawing: | 116-0437 |
| UL approval: Control drawing: | 116-0438 (cULus) |
| IECEx approval: IECEx certificate: | IECEx BAS 05.0004X IECEx CML 19.0040X |
| IECEx approval: IECEx marking: | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Country of Origin: | Singapur |
| EAN: | 4050143058723 |
| Weight: | 0.14 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |