TW2000
Infrared temperature sensor. TW-030KLBM30-KFDKG/US
Reliable, non-contact temperature measurement of objects with very high temperatures. For applications in the steel and glass industries. Intuitive setting of analogue output and switching output via pushbutton. Clearly visible display for showing the current temperature. Robust housing and scratch-resistant precision lens for use in harsh industrial environments
Number of inputs and outputs: | Number of digital outputs: 1; Number of analogue outputs: 1 |
Measuring range: | 0...999.5 °C 32...1831 °F |
0...999.5 °C: | 32...1831 °F |
Application: | asphalt; coated metal; liquids; glass; rubber; wood; ceramics; plastics; lacquers; food products; paper; fabric |
Operating voltage [V]: | 18...32 DC; (to SELV/PELV) |
Current consumption [mA]: | < 50 |
Min. insulation resistance [MΩ]: | 100; (50 V DC) |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | < 1 |
Number of inputs and outputs: | Number of digital outputs: 1; Number of analogue outputs: 1 |
Test input: | type 3 (IEC 61131-2) |
Total number of outputs: | 2 |
Output signal: | switching signal; analogue signal; IO-Link; (configurable) |
Electrical design: | PNP |
Number of digital outputs: | 1 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 150 |
Number of analogue outputs: | 1 |
Analogue current output [mA]: | 4...20 |
Max. load [Ω]: | 500 |
Short-circuit protection: | yes |
Type of short-circuit protection: | pulsed |
Short-circuit proof: | yes |
Overload protection: | yes |
Wave length range [µm]: | 8...14 |
Measuring range: | 0...999.5 °C 32...1831 °F |
0...999.5 °C: | 32...1831 °F |
Set point SP: | 1...999.5 °C 34...1831 °F |
1...999.5 °C: | 34...1831 °F |
Reset point rP: | 0...998.5 °C 32...1829 °F |
0...998.5 °C: | 32...1829 °F |
Analogue start point: | 0...949.5 °C 32...1741.1 °F |
0...949.5 °C: | 32...1741.1 °F |
Analogue end point: | 50...999.5 °C 122...1831 °F |
50...999.5 °C: | 122...1831 °F |
In steps of: | 0.5 °C 1 °F |
0.5 °C: | 1 °F |
Resolution of switching output [K]: | 0.5 |
Resolution of analogue output [K]: | 0.2; (+ 0.03% of the set measuring span) |
Resolution of display [K]: | 0.5 |
Accuracy [K]: | < ± 1 %; (of measured value, min. 2 K (degree of emission = 1, T = 23 °C)) |
Repeatability [K]: | 1 |
Response time [ms]: | 100 |
Adjustment of the switch point: | programming buttons |
Parameter setting options: | analogue range; normally open / normally closed; switch-on/switch-off delay; Damping; Peakhold; emissivity; simulation function |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
SDCI standard: | IEC 61131-9 |
IO-Link device ID: | 716 d / 00 02 CC h |
SIO mode: | yes |
Required master port type: | A |
Process data analogue: | 16 |
Process data binary: | 1 |
Min. process cycle time [ms]: | 3.6 |
Ambient temperature [°C]: | 0...65 |
Storage temperature [°C]: | -20...80 |
Max. relative air humidity [%]: | 95; (non condensing) |
Protection: | IP 65 |
EMC: | DIN EN 61000-6-2 DIN EN 61000-6-4 |
Shock resistance: | DIN EN 60068-2-27 30 g (11 ms) |
DIN EN 60068-2-27: | 30 g (11 ms) |
Vibration resistance: | DIN EN 60068-2-6 5 g (10...2000 Hz) |
DIN EN 60068-2-6: | 5 g (10...2000 Hz) |
MTTF [years]: | 88 |
Weight [g]: | 411.5 |
Housing: | threaded type |
Dimensions [mm]: | M30 x 1.5 |
Thread designation: | M30 x 1.5 |
Materials: | threaded sleeve: stainless steel (1.4305 / 303); polyester |
Lens material: | Infrared transparent crystal lens with anti-reflex coating |
Display: | Display unit 2 x LED, yellow switching status 1 x LED, yellow function display 7-segment LED display, 4-digit measured values 7-segment LED display, 4-digit |
Display unit: | 2 x LED, yellow |
switching status: | 1 x LED, yellow |
function display: | 7-segment LED display, 4-digit |
measured values: | 7-segment LED display, 4-digit |
Operating elements: | 3 pushbuttons |
3: | pushbuttons |
Accessories (supplied): | lock nuts: 2 |
Remarks: | Use a screened cable to protect infrared temperature sensors from interference. The screen must be connected to the housing of the sensor via the connector. |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12 |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.41 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |