Ifm TA2262

Temperature transmitter. TA-250CLED06-- /US

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Hygienic design for the requirements of the food and beverage industry. Particularly good response dynamics and very short power-on delay time. High precision across the entire temperature measurement range. Precise analogue output and user-friendly communication via IO-Link. Robust stainless steel housing with high protection rating and high pressure rating

Technical parameters

Number of inputs and outputs: Number of analogue outputs: 1
Measuring range [°C]: -50...200
Process connection: diameter Ø 6 mm
Installation length EL [mm]: 250
Measuring element: 1 x Pt 1000; (to DIN EN 60751, class A)
Media: liquids and gases
Pressure rating [bar]: 160
Vacuum resistance [mbar]: -1000
Operating voltage [V]: 18...32 DC; ("supply class 2" to cULus)
Current consumption [mA]: < 50
Protection class: III
Reverse polarity protection: yes
Power-on delay time [s]: 2
Number of inputs and outputs: Number of analogue outputs: 1
Total number of outputs: 1
Output signal: analogue signal; IO-Link; (configurable)
Number of analogue outputs: 1
Analogue current output [mA]: 4...20
Max. load [Ω]: 250; ((18...19 V); 19...32 V: 300 Ω)
Short-circuit protection: yes
Overload protection: yes
Measuring range [°C]: -50...200
Factory setting: 0...200 °C
Resolution of analogue output [K]: 0.04
Precision analogue output [K]: ± 0,3 + (± 0,1 % MS)
Temperature coefficient [% of the span / 10 K]: 0,1; (in case of deviation from the reference condition 25 ± 5 °C)
Dynamic response T05 / T09 [s]: < 0,5 / < 2
Communication interface: IO-Link
Transmission type: COM2 (38,4 kBaud)
IO-Link revision: 1.1
Ambient temperature [°C]: -25...80
Note on ambient temperature: at medium temperature: < 160 °C -25...60 °C at medium temperature: < 200 °C
Storage temperature [°C]: -40...100
Protection: IP 67; IP 68; IP 69K
EMC: DIN EN 61000-6-2 DIN EN 61000-6-3
Shock resistance: DIN IEC 68-2-27 50 g (11 ms)
DIN IEC 68-2-27: 50 g (11 ms)
Vibration resistance: DIN IEC 68-2-6 10 g (10...2000 Hz)
DIN IEC 68-2-6: 10 g (10...2000 Hz)
MTTF [years]: 334
Note on approval: factory certificate available as download at www.factory-certificate.ifm
UL approval: UL Approval no. K002
UL Approval no.: K002
Weight [g]: 174
Dimensions [mm]: Ø 18.7
Materials: stainless steel (1.4404 / 316L); PEI; FKM
Materials (wetted parts): stainless steel (1.4404 / 316L)
Process connection: diameter Ø 6 mm
Surface characteristics Ra/Rz of the wetted parts: Ra: < 0.6
Probe diameter [mm]: 6
Installation length EL [mm]: 250
Remarks: MS = set measuring span
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12

Logistic parameters

ECCN:
Country of Origin: US
EAN:
Weight: 0.17 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m