Ifm SV5614

Vortex flow meter with display. SVN12XXX50KG/US-100

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Reliable detection of flow and medium temperature. Precise linearized analogue output. Display can be rotated for optimum alignment. Clearly readable colour display with red/green colour change. Suitable for water, deionised water and cooling water

Technical parameters

Number of inputs and outputs: Number of analogue outputs: 2
Process connection: threaded connection 1/2" NPT DN10
Measuring range [°F]: 14...194
Special feature: Gold-plated contacts
Application: for industrial applications
Media: water
Medium temperature [°F]: 14...194
Pressure rating [bar]: 12
Pressure rating [psi]: 174
Note on pressure rating: up to 40 °C
MAWP (for applications according to CRN) [bar]: 4.8
Operating voltage [V]: 18...30 DC
Current consumption [mA]: < 30
Min. insulation resistance [MΩ]: 100; (500 V DC)
Protection class: III
Reverse polarity protection: yes
Power-on delay time [s]: < 3
Number of inputs and outputs: Number of analogue outputs: 2
Total number of outputs: 2
Output signal: analogue signal
Number of analogue outputs: 2
Analogue current output [mA]: 4...20
Max. load [Ω]: 500
Short-circuit protection: yes
Overload protection: yes
Measuring range: 32...634 gph 0.55...10.55 gpm
32...634 gph: 0.55...10.55 gpm
Display range: 0...760 gph 0...12.7 gpm
0...760 gph: 0...12.7 gpm
Resolution: 2 gph 0.05 gpm
2 gph: 0.05 gpm
Analogue start point ASP: 0...508 gph 0...8.45 gpm
0...508 gph: 0...8.45 gpm
Analogue end point AEP: 126...634 gph 2.1...10.55 gpm
126...634 gph: 2.1...10.55 gpm
In steps of: 2 gph 0.05 gpm
2 gph: 0.05 gpm
Measuring dynamics: 1:20
Measuring range [°F]: 14...194
Display range [°F]: -22...230
Resolution [°F]: 1
Analogue start point [°F]: 14...158
Analogue end point [°F]: 50...194
In steps of [°F]: 1
Accuracy (in the measuring range): ± 2 % MEW
Repeatability: ± 0,5 % MEW
Accuracy [K]: ± 1
Response time [s]: 1; (dAP = 0)
Damping for the switching output dAP [s]: 0...5
Dynamic response T05 / T09 [s]: T09 = 6
Parameter setting options: Damping for the analogue output dAA; Display unit
Ambient temperature [°F]: 32...140
Note on ambient temperature: medium temperature < 176 °F medium temperature < 194 °F: 32...122 °F
Storage temperature [°F]: -4...176
Protection: IP 65; IP 67
EMC: DIN EN 61000-6-2 DIN EN 61000-6-3
Shock resistance: DIN EN 60068-2-27 5 g (11 ms)
DIN EN 60068-2-27: 5 g (11 ms)
Vibration resistance: DIN EN 60068-2-6 with water / 10...50 Hz 1 mm with water / 50...2000 Hz 2 g
DIN EN 60068-2-6: with water / 10...50 Hz 1 mm
MTTF [years]: 342
UL approval: UL Approval no. I002
UL Approval no.: I002
Pressure Equipment Directive: Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]: 466
Materials: stainless steel (1.4404 / 316L); PC; PBT+PC-GF30; PPS; TPE-U
Materials (wetted parts): stainless steel (1.4404 / 316L); ETFE; PA 6T; PPS; FKM
Tightening torque [Nm]: 30
Process connection: threaded connection 1/2" NPT DN10
Remarks: MW = measured value MEW = Final value of the measuring range
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.47 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m