Precise measurement of flow, consumption and medium temperature. Suitable for water, oils and glycol solutions. For installation in pipes. With switching output, analogue output and pulse output. Clearly visible 4-digit LED display

Technical parameters

Number of inputs and outputs: Number of digital outputs: 2; Number of analogue outputs: 1
Process connection: threaded connection G 3/4 flat seal
Measuring range [°C]: -10...80
Special feature: Gold-plated contacts
Application: totaliser function; for industrial applications
Installation: connection to pipe by means of an adapter
Media: water; glycol solutions; coolants; oil
Note on media: low-viscosity oils with viscosity: 7...40 mm²/s (40 °C) high-viscosity oils with viscosity: 30...68 mm²/s (40 °C)
Medium temperature [°C]: -10...80
Pressure rating [bar]: 16
Pressure rating [Mpa]: 1.6
Operating voltage [V]: 19...30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]: 100
Min. insulation resistance [MΩ]: 100; (500 V DC)
Protection class: III
Reverse polarity protection: yes
Power-on delay time [s]: 10
Number of inputs and outputs: Number of digital outputs: 2; Number of analogue outputs: 1
Inputs: counter reset
Total number of outputs: 2
Output signal: switching signal; analogue signal; pulse signal; (configurable)
Electrical design: PNP/NPN
Number of digital outputs: 2
Output function: normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]: 2
Permanent current rating of switching output DC [mA]: 250; (per output)
Number of analogue outputs: 1
Analogue current output [mA]: 4...20; (scalable)
Max. load [Ω]: 500
Analogue voltage output [V]: 0...10; (scalable)
Min. load resistance [Ω]: 2000
Pulse output: flow rate meter
Short-circuit protection: yes
Type of short-circuit protection: pulsed
Overload protection: yes
Measuring range: 0...50 l/min 0...3 m³/h
0...50 l/min: 0...3 m³/h
Display range: 0...60 l/min 0...3.6 m³/h
0...60 l/min: 0...3.6 m³/h
Resolution: 0.1 l/min 0.005 m³/h
0.1 l/min: 0.005 m³/h
Set point SP: 0.1...50 l/min 0.005...3 m³/h
0.1...50 l/min: 0.005...3 m³/h
Reset point rP: 0...49.9 l/min 0...2.995 m³/h
0...49.9 l/min: 0...2.995 m³/h
Analogue start point ASP: 0...40 l/min 0...2.4 m³/h
0...40 l/min: 0...2.4 m³/h
Analogue end point AEP: 10...50 l/min 0.6...3 m³/h
10...50 l/min: 0.6...3 m³/h
Max. flow rate: 60 l/min 3.6 m³/h
60 l/min: 3.6 m³/h
In steps of: 0.1 l/min 0.005 m³/h
0.1 l/min: 0.005 m³/h
Pulse value: 0.1 l...1 000 000 m³
Pulse length [s]: 0,05...2
Measuring range [°C]: -10...80
Resolution [°C]: 0.2
Set point SP [°C]: -9.8...80
Reset point rP [°C]: -10...79.8
Analogue start point [°C]: -10...62
Analogue end point [°C]: 8...80
In steps of [°C]: 0.2
Accuracy (in the measuring range): < ± (3 % MW + 0,2 % MEW) / < ± (5 % MW + 0,5 % MEW); (water; glycol: 35%; oil: viscosity 68 mm²/s at 40 °C)
Repeatability: 0,1 l/min; 6 l/h; 0,006 m³/h
Accuracy [K]: ± 3 (Q > 1 l/min)
Response time [s]: 0.25; (dAP = 0)
Delay time programmable dS, dr [s]: 0...50
Damping for the switching output dAP [s]: 0...1
Dynamic response T05 / T09 [s]: T09 = 70 (Q > 5 l/min); (water)
Parameter setting options: Flow monitoring; quantity meter; Preset counter; Temperature monitoring
Ambient temperature [°C]: -10...60
Storage temperature [°C]: -25...80
Protection: IP 67
EMC: EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-5 Surge 0,5 kV EN 61000-4-6 HF conducted 10 V
EN 61000-4-2 ESD: 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated: 10 V/m
EN 61000-4-4 Burst: 2 kV
EN 61000-4-5 Surge: 0,5 kV
EN 61000-4-6 HF conducted: 10 V
Shock resistance: DIN IEC 68-2-27 20 g (11 ms)
DIN IEC 68-2-27: 20 g (11 ms)
Vibration resistance: DIN IEC 68-2-6 5 g (10...2000 Hz)
DIN IEC 68-2-6: 5 g (10...2000 Hz)
MTTF [years]: 175
Pressure Equipment Directive: Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]: 1551.5
Materials: housing: AlMgSi0,5 anodised; Sealing: FKM; connector housing: brass Optalloy-plated; PA 6.6; cover film: PA
Materials (wetted parts): stainless steel (1.4404 / 316L); FKM; PES; Centellen 200
Process connection: threaded connection G 3/4 flat seal
Display: Display unit 6 x LED, green (l/min, m³/h, l, m³, 10³, °C) switching status 2 x LED, yellow measured values alphanumeric display, 4-digit programming alphanumeric display, 4-digit
Display unit: 6 x LED, green (l/min, m³/h, l, m³, 10³, °C)
switching status: 2 x LED, yellow
measured values: alphanumeric display, 4-digit
programming: alphanumeric display, 4-digit
Accessories (supplied): sealings: 2, Centellen
Accessories (optional): adapter for pipe: 1 x R1/2, stainless steel, E40178 adapter for pipe: 1 x R1/2, brass, E40151
Remarks: MW = measured value MEW = Final value of the measuring range sealing: only with supplied Centellen seals
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Moulded body: brass, Optalloy-plated; Contacts: gold-plated

Logistic parameters

ECCN:
Country of Origin: US
EAN:
Weight: 1.55 kg
Length: 0.00 m
Width: 0.00 m