SI1106
Flow monitor. SID10ADTFKOW/LS-100-IRF
Reliable monitoring of liquids and gases in pipes. Variable process connection using adapters. Easy setting of the switch points for quick set-up. Robust housing for use in harsh industrial environments. LED bar graph for indication of switch point and flow
Number of inputs and outputs: | Number of digital outputs: 1 |
Process connection: | M18 x 1,5 internal thread |
Media: | Liquids; Gases; aggressive media |
Medium temperature [°C]: | -25...80 |
Pressure rating [bar]: | 300 |
Medium temperature [°C]: | -25...80 |
Medium temperature [°C]: | -25...80 |
Operating voltage tolerance [%]: | -5...10 |
Operating voltage [V]: | 85...265 AC |
Nominal voltage AC [V]: | < 240 |
Protection class: | II |
Reverse polarity protection: | no |
Power-on delay time [s]: | 15; (optically indicated) |
Number of inputs and outputs: | Number of digital outputs: 1 |
Total number of outputs: | 1 |
Output signal: | switching signal |
Electrical design: | relay |
Number of digital outputs: | 1 |
Output function: | normally open / normally closed; (parameterisable) |
Contact rating: | 3 A (250 V AC / 30 V DC); (number of switching cycles: 20 million mechanically; switching cycles at 3 A load: 100,000 electrical; type of switch-off: normally open) |
Short-circuit proof: | no |
Overload protection: | no |
Probe length L [mm]: | 45 |
Setting range [cm/s]: | 3...300 |
Greatest sensitivity [cm/s]: | 3...60 |
Setting range [cm/s]: | 200...3000 |
Greatest sensitivity [cm/s]: | 200...800 |
Temperature gradient [K/min]: | 300 |
Response time [s]: | 1...10 |
Response time [s]: | 1...10 |
Response time [s]: | 1...10 |
Adjustment of the switch point: | pushbutton |
Ambient temperature [°C]: | -25...80 |
Protection: | IP 67 |
Shock resistance: | DIN IEC 68-2-27 50 g (11 ms) |
DIN IEC 68-2-27: | 50 g (11 ms) |
Vibration resistance: | DIN EN 60068-2-6 20 g (55...2000 Hz) |
DIN EN 60068-2-6: | 20 g (55...2000 Hz) |
MTTF [years]: | 224 |
Weight [g]: | 254.4 |
Dimensions [mm]: | M18 x 1.5 |
Thread designation: | M18 x 1.5 |
Materials: | PBT-GF20 |
Materials (wetted parts): | titanium (3.7035); O-ring: FFKM 8 x 1,5 |
Process connection: | M18 x 1,5 internal thread |
Display: | function 10 x LED, three-colour |
function: | 10 x LED, three-colour |
Required protection: | miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting |
Remarks: | Recommendation Check the safe functioning of the unit after a short circuit. |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x 1/2" |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.25 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |